Loop Operation Mode
Type of Loop Input
1
Configuring the Module
You configure the module by setting words and bits for each loop in
Configuration Block, N10:0–100, which your ladder logic uses to load
the module's M1 file. We cover bit selections and word descriptions.
Refer to the table at the end of this chapter for selections, units, and
defaults.
Word 1, Bits 0 and 1 for Channel 1
Use these bits to select how you want the loop to perform:
Mode of Loop Operation
monitor the loop to indicate temperature and alarms
perform PID loop control with temperature indication and
alarms
disable the loop
invalid setting
Word 1, Bits 2-5 for Channel 1
Use the following bits to select type J or K thermocouple; any other
bit setting is invalid:
TC
type J
type K
05
04
03
02
0
0
0
0
0
0
0
1