2. BACnet MS/TP, CIM 300 setup

2.1 BACnet bus topology

Grundfos CIM/CIU 300 is connected as a BACnet MS/TP master
directly to the BACnet MS/TP network.
M
S
LT
BR
M
S
Example of BACnet MS/TP network
Pos.
Description
M
Master
S
Slave
LT
Line Termination
BR
Bias Resistors
BACnet MS/TP is a multi-master system, meaning that there can be
more than one master on the network. It uses a token to control
access to the bus network. A master node may initiate the
transmission of a data telegram when it holds the token. Both
master and slave nodes may transmit data telegrams in response to
requests from master nodes, but slaves never hold the token.
Master nodes pass the token between them.
A BACnet MS/TP segment is a single contiguous medium to which
BACnet nodes are attached. Segments can be connected by use of
repeaters or bridges, thus forming networks.
Multiple networks may be interconnected by BACnet routers to form
a BACnet inter-network.
2.1.1 Line termination resistors
Line termination must be connected at each of the two ends of the
segment medium. CIM/CIU 300 has optional line termination
resistor on board.
2.1.2 Bias resistors
At least one set, and no more than two sets, of network bias
resistors must exist for each segment so that an undriven
communications line will be held in a guaranteed logical one state.
The bias provides a reliable way for stations to detect the presence
or absence of signals on the line. An unbiased line will take an
indeterminate state in the absence of any driving node.
CIM/CIU 300 has no bias resistors.
8
S
M
LT
S

2.2 CIM 300 BACnet module

1 2 3
4
5
CIM 300 BACnet module
Pos.
Designation
Description
BACnet Plus terminal, RS-485 positive
1
Plus
data signal
BACnet Minus terminal, RS-485 negative
2
Minus
data signal
3
Ground
BACnet ground terminal
On and off switches for termination
4
SW1/SW2
resistor
Switches for selecting the BACnet
5
SW3/SW4/SW5
transmission speed and the default or
custom Device Object Instance Number
Red and green status LED for BACnet
6
LED1
communication
Red and green status LED for internal
7
LED2
communication between CIM 300 and the
booster system
Hexadecimal rotary switch for setting the
8
SW6
BACnet MAC address (four most
significant bits)
Hexadecimal rotary switch for setting the
9
SW7
BACnet MAC address (four least
significant bits)
8
9
6
7