Analog Outputs; Analog Values - Grundfos CIM 300 User Manual

Bacnet for grundfos level control lc 2x1 and lc 2x2
Table of Contents

Advertisement

ID
Object name
AI, 40
Sensor present status
AI, 41
Pump1 Alarms 1-4 and warnings 1-4
AI, 42
Pump2 Alarms 1-4 and warnings 1-4
AI, 43
Pump1MotorVoltage
AI, 44
Pump2MotorVoltage
AI, 45
Pump1CosPhi
AI, 46
Pump2CosPhi

5.7 Analog outputs

Object for setting a new setpoint in the pump.
ID
Object name
AO, 0
SetHighLevel
AO, 1
SetDryRunningLevel
AO, 2
SetStartLevelPump1
AO, 3
SetStopLevelPump1
AO, 4
SetStartLevelPump2

5.8 Analog values

Objects for configuration of the module, the unit and the pump.
ID
Object name
Custom device object instance
AV, 0
number
AV, 1
Product time and date
AV, 2
CIMSoftwareVersionNumber
R/W
Description
Values are transmitted in the following order:
bit 0: Flow sensor present
bit 1: Power/energy sensor present
bit 2: AI sensor 1 present
bit 3: AI sensor 2 present
bit 4: AI sensor 3 present
bit 5: AI sensor 4 present
bit 6: AI sensor 5 present
bit 7: Turbidity sensor present
R
bit 8: pH sensor present
bit 9: Conductivity sensor present
bit 10: Pulse flow meter present
bit 11: Pressure sensor present
bit 12: Level sensor present
Bit values indicate the following:
bit value 0: Sensor not present
bit value 1: Sensor present
bit 0 - Status pump 1 warning 1
bit 1 - Status pump 1 warning 2
bit 2 - Status pump 1 warning 3
bit 3 - Status pump 1 warning 4
R
bit 8 - Status pump 1 alarm 1
bit 9 - Status pump1 alarm 2
bit 10 - Status pump 1 alarm 3
bit 11 - Status pump 1 alarm 4 (hex)
bit 0 - Status pump 2 warning 1
bit 1 - Status pump 2 warning 2
bit 2 - Status pump 2 warning 3
bit 3 - Status pump 2 warning 4
R
bit 8 - Status pump 2 alarm 1
bit 9 - Status pump 2 alarm 2
bit 10 - Status pump 2 alarm 3
bit 11 - Status pump 2 alarm 4 (hex)
R
Pump1 MotorVoltage
R
Pump2 MotorVoltage
R
Pump1 CosPhi
R
Pump2 CosPhi
R/W
Notes
W
Set high level in centimetres.
W
Set dry running level in centimetres.
W
Set start level for pump 1 in centimetres.
W
Set stop level for pump 1 in centimetres.
W
Set start level for pump 2 in centimetres.
R/W
Notes
Present_Value range: 0-0x3FFFFE.
R/W
Default Present_Value: 0xE7. [RD = 0]
R/W
Set clock in UNIX format.
R
Decimal value
Unit
LC 2X1
LC 2X2
-
-
-
V
V
CosPhi
CosPhi
Unit
LC 2X1
LC 2X2
cm
cm
cm
cm
cm
Unit
LC 2X1
LC 2X2
-
s
-
-
19