ID
Object name
AI, 40
Sensor present status
AI, 41
Pump1 Alarms 1-4 and warnings 1-4
AI, 42
Pump2 Alarms 1-4 and warnings 1-4
AI, 43
Pump1MotorVoltage
AI, 44
Pump2MotorVoltage
AI, 45
Pump1CosPhi
AI, 46
Pump2CosPhi
5.7 Analog outputs
Object for setting a new setpoint in the pump.
ID
Object name
AO, 0
SetHighLevel
AO, 1
SetDryRunningLevel
AO, 2
SetStartLevelPump1
AO, 3
SetStopLevelPump1
AO, 4
SetStartLevelPump2
5.8 Analog values
Objects for configuration of the module, the unit and the pump.
ID
Object name
Custom device object instance
AV, 0
number
AV, 1
Product time and date
AV, 2
CIMSoftwareVersionNumber
R/W
Description
Values are transmitted in the following order:
•
bit 0: Flow sensor present
•
bit 1: Power/energy sensor present
•
bit 2: AI sensor 1 present
•
bit 3: AI sensor 2 present
•
bit 4: AI sensor 3 present
•
bit 5: AI sensor 4 present
•
bit 6: AI sensor 5 present
•
bit 7: Turbidity sensor present
R
•
bit 8: pH sensor present
•
bit 9: Conductivity sensor present
•
bit 10: Pulse flow meter present
•
bit 11: Pressure sensor present
•
bit 12: Level sensor present
Bit values indicate the following:
•
bit value 0: Sensor not present
•
bit value 1: Sensor present
•
bit 0 - Status pump 1 warning 1
•
bit 1 - Status pump 1 warning 2
•
bit 2 - Status pump 1 warning 3
•
bit 3 - Status pump 1 warning 4
R
•
bit 8 - Status pump 1 alarm 1
•
bit 9 - Status pump1 alarm 2
•
bit 10 - Status pump 1 alarm 3
•
bit 11 - Status pump 1 alarm 4 (hex)
•
bit 0 - Status pump 2 warning 1
•
bit 1 - Status pump 2 warning 2
•
bit 2 - Status pump 2 warning 3
•
bit 3 - Status pump 2 warning 4
R
•
bit 8 - Status pump 2 alarm 1
•
bit 9 - Status pump 2 alarm 2
•
bit 10 - Status pump 2 alarm 3
•
bit 11 - Status pump 2 alarm 4 (hex)
R
Pump1 MotorVoltage
R
Pump2 MotorVoltage
R
Pump1 CosPhi
R
Pump2 CosPhi
R/W
Notes
W
Set high level in centimetres.
W
Set dry running level in centimetres.
W
Set start level for pump 1 in centimetres.
W
Set stop level for pump 1 in centimetres.
W
Set start level for pump 2 in centimetres.
R/W
Notes
Present_Value range: 0-0x3FFFFE.
R/W
Default Present_Value: 0xE7. [RD = 0]
R/W
Set clock in UNIX format.
R
Decimal value
Unit
LC 2X1
LC 2X2
-
●
●
-
●
●
-
●
●
V
●
●
V
●
●
CosPhi
●
●
CosPhi
●
●
Unit
LC 2X1
LC 2X2
cm
●
●
cm
●
●
cm
●
●
cm
●
●
cm
●
●
Unit
LC 2X1
LC 2X2
-
●
●
s
●
●
-
-
●