GRUNDFOS INSTRUCTIONS
CIM 500 Ethernet module
Installation and operating instructions
CIM 500 Ethernet
Installation and operating instructions
Other languages
http://net.grundfos.com/qr/i/98407037

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CIM 500 and is the answer not in the manual?

Questions and answers

Summary of Contents for Grundfos CIM 500

  • Page 1 GRUNDFOS INSTRUCTIONS CIM 500 Ethernet module Installation and operating instructions CIM 500 Ethernet Installation and operating instructions Other languages http://net.grundfos.com/qr/i/98407037...
  • Page 3 CIM 500 Ethernet module English (GB) Installation and operating instructions ........4 Deutsch (DE) Montage- und Betriebsanleitung .
  • Page 4: Table Of Contents

    Abbreviations ....5 moderate personal injury. CIM 500 Ethernet module ..6 The hazard statements are structured in the following Installation .
  • Page 5: Applications

    2. Applications Hyper Text Transfer Protocol. The HTTP protocol commonly used to navigate The CIM 500 Ethernet module enables data the World Wide Web. transmission between an Industrial Ethernet network and a Grundfos product. IANA Internet Assigned Numbers Authority. The module supports various Industrial Ethernet Internet Protocol.
  • Page 6: Cim 500 Ethernet Module

    2.2 CIM 500 Ethernet module Related information 5. Data activity and link LEDs CIM 500 Ethernet module Pos. Designation Description Industrial Ethernet RJ45 ETH1 connector 1 Industrial Ethernet RJ45 ETH2 connector 2 Data activity LED for RJ45 DATA1 connector 1 Link LED for RJ45 connector...
  • Page 7: Installation

    Networks (VPNs) to ensure a secured connection. Consider contacting an IT Infrastructure Specialist to establish such a solution. For CIM 500 in mode 4, GRM IP (Grundfos Remote Management), or in mode 5 (GiC), the firewall must accept connections initialised by the Grundfos...
  • Page 8: Connecting The Ethernet Cable

    Ethernet ports. Each Ethernet port has its own MAC address, and CIM 500 has a built-in switch which means that the cable can run another 100 metres whenever passing a CIM 500 module.
  • Page 9: Selection Of Industrial Ethernet Protocol

    It can be given a fixed value via EtherNet/IP the webserver, or it can use a DHCP server. IP settings for GRM IP for Grundfos Remote Modbus TCP This assigned Modbus TCP Management. Requires a contract with address must be different from Grundfos.
  • Page 10: Connection To The Webserver

    PC parallel to the router (RJ45 port 1) CIM 500, proceed as follows: at CIM 500 RJ45 port 2. Look at the router webserver 1. Connect the PC and the module using an which address the router assigns to CIM 500. Then Ethernet cable.
  • Page 11: Status Leds

    The module is in cyclic data green exchange mode. Resetting to factory settings. Flashing red Flashing red Wrong or missing PROFINET IO After 20 seconds, CIM 500 and green configuration. See the section (3 Hz, duty restarts. about fault finding, PROFINET IO. cycle 50 %)
  • Page 12: Data Activity And Link Leds

    The module is switched off. DATA1 and DATA2 No internal communication between Flashing red These yellow LEDs indicate data traffic for the RJ45 CIM 500 and the Grundfos product. connector in question. Permanently The module does not support the Grundfos product connected.
  • Page 13: Fault Finding

    You can detect faults in a module by observing the status of the two status LEDs. Related information The prerequisite is that CIM 500 is fitted in a 4. Status LEDs Grundfos product or CIM 500 fitted in a CIU 500.
  • Page 14 Related information A.1. Webserver configuration 6.1.7 LED1 is pulsing red, 0.3 Hz Cause Remedy The connection to the master is lost. • Check the cables. • Check that the master is running. 6.1.8 LED1 is permanently red and green at the same time Cause Remedy Error in firmware download.
  • Page 15: Modbus Tcp Or Bacnet Ip

    Modbus should be selected or in position status of the two status LEDs. "2" if BACnet should be selected. The prerequisite is that CIM 500 is fitted in a Grundfos product or in a CIU 500. Related information 4. Status LEDs 6.2.1 Both LEDs remain off...
  • Page 16 6.2.6 LED2 is permanently red and green at the same time Cause Remedy Memory fault. • Replace the module.
  • Page 17: Ethernet/Ip

    You can detect faults in a module by observing the Ensure that SW1 is in position "3". status of the two status LEDs. The prerequisite is that CIM 500 is fitted in a Grundfos product or in a CIU 500. 6.3.1 Both LEDs remain off Both LEDs remain off when the power supply is connected.
  • Page 18 Related information A.1. Webserver configuration 6.3.8 LED2 is permanently red and green at the same time Cause Remedy Memory fault. • Replace the module.
  • Page 19: Grm Ip

    You can detect faults in a module by observing the GRM IP or position "5" to select GiC. status of the two status LEDs. The prerequisite is that CIM 500 is fitted in a Grundfos product or in a CIU 500. This requires a contract with Grundfos.
  • Page 20 Remedy No connection to the GRM server. • Check that you use the lowest MAC address (lowest number) of the two ports of CIM 500. See the sticker on the module. • It requires a contract with Grundfos and granted access to GRM or GiC.
  • Page 21: Technical Data

    Modbus TCP • BACnet IP Industrial Ethernet protocols • EtherNet/IP • GRM IP • 5 VDC ± 5 %, I 350 mA Supply voltage max. -25 to +70 °C Min./max. storage temperature -13 to +158 °F Requires a contract with Grundfos.
  • Page 22: Profinet Technical Specifications

    7.1 PROFINET technical specifications • PROFINET device according to Conformance Class B • Media Redundancy Protocol (MRP) Client Functionality PROFINET RT • System redundancy S2 • Multicast provider and subscriber Minimum cycle time PROFINET RT 250 μs 2 for cyclic data Number of IO connections per controller 1 for parameter set Maximum number of IO data...
  • Page 23: Modbus Tcp Technical Specifications

    It can be enabled via the watchdog register in the device profile. Certificate To optimise data security when using Modbus TCP via a cellular router, Grundfos strongly recommends that the cellular data connection is based on a private APN with static IP and with no access to public Internet.
  • Page 24 Data sharing services • WritePropertyMultiple • SubscribeCOV • ConfirmedCOVNotification • UnconfirmedCOVNotification • Who-is / I-am Device management services • Who-has / I-have • DeviceCommunicationControl Network watchdog timer. Time-out is configurable via the Watchdog CIM 500 web page. Certificate BTL listing...
  • Page 25: Ethernet/Ip Technical Specifications

    Device Level Ring (DLR) protocol (announce-based ring node). • Quality of Service (QoS). • IPv4 Address Conflict Detection (ACD). Communication watchdog with fixed 5 seconds time-out. Watchdog It can be enabled via the CIM 500 web page. Certificate Plugfest December 2018, Conformance July 2019.
  • Page 26: Disposing Of The Product

    1. Use the public or private waste collection service. 2. If this is not possible, contact the nearest Grundfos company or service workshop. The crossed-out wheelie bin symbol on a product means that it must be disposed of separately from household waste.
  • Page 27 Appendix A A.1. Webserver configuration The built-in webserver offers easy monitoring of the CIM 500 module and makes it possible to configure the selected Industrial Ethernet protocol. Using the webserver, you can also update the firmware of the CIM 500 module and store or restore settings, among other functions.
  • Page 28 3. Select "Change adapter options". 4. Right-click "Ethernet" and select "Properties". 5. Select properties for "Internet Protocol Version 4 (TCP/IPv4)". 6. Select the "Alternate Configuration" tab and enter the user-configured IP address and subnet mask you would like to assign to your PC.
  • Page 29 • at least one numeric or special character. When logging in, you have four attempts before a back-off algorithm starts an exponentially increasing time delay between each attempt. Power cycling CIM 500 resets the back-off algorithm.
  • Page 30 Related information A.1.13. User Management...
  • Page 31 A.1.4. System information System information...
  • Page 32 A.1.5. PROFINET IO configuration This web page is used to configure all the parameters relevant to the PROFINET IO protocol standard. Real Time Ethernet Protocol Configuration - PROFINET IO...
  • Page 33 This field is read-only. The IP address is assigned from the PLC. PROFINET IO is not IP Address allowed to share the IP address with a CIM 500 webserver. Subnet Mask This field is read-only. The subnet mask is assigned from the PLC.
  • Page 34 Configuration of the static IP address if a DHCP server is not used. Modbus TCP is not IP Address allowed to share the IP address with the CIM 500 webserver. Subnet Mask Configuration of the subnet mask if a DHCP server is not used.
  • Page 35 Enter the Device Instance number. The default number is 227000. The Device Instance must Device Instance be unique in the BACnet network. For Grundfos, the first three digits of the number is 227 and it is fixed. The last three digits can be changed.
  • Page 36 Object Description Custom device If ticked, CIM 500 is configured to use a BACnet custom device instance number. instance enable Foreign Device If ticked, CIM 500 is configured as a foreign device. IP Address Enter the foreign IP address. UDP Port Enter the foreign UDP port number.
  • Page 37 A.1.8. EtherNet/IP configuration This web page is used to configure all the parameters relevant to the EtherNet/IP protocol standard. Real Time Ethernet Protocol Configuration - EtherNet/IP...
  • Page 38 Gateway Configuration of the gateway address if a DHCP server is not used. The CIM 500 module can be configured to automatically obtain its EtherNet/IP network Use DHCP settings from a DHCP server, if available on the network. Default: No use of DHCP.
  • Page 39 A.1.9. GRM IP configuration By default, the GRM server URL and DHCP are activated on the GRM webserver. You need a contract with Grundfos and an external router with Internet connection to gain access to the GRM server. Real Time Ethernet Protocol Configuration - GRM IP...
  • Page 40 Gateway Configuration of the gateway address if a DHCP server is not used. The CIM 500 module can be configured to automatically obtain its EtherNet/IP network Use DHCP settings from a DHCP server, if available on the network. Default: No use of DHCP.
  • Page 41 A.1.11. Network settings This web page is used to configure the network settings of the webserver and of the GENIpro TCP protocol. The network settings here are also used for BACnet IP. Additional configuration of BACnet IP is done in the Real Time Ethernet Protocol menu.
  • Page 42 A.1.12. GENIpro TCP port settings This web page is only present when the Modbus TCP protocol has been selected, SW1 is in position 1. The module can connect to a Grundfos PC Tool and communicate with the product via the GENIpro TCP protocol.
  • Page 43 A.1.13. User Management A login is required for any change of the CIM 500 settings, and this web page is used to configure the username and password. See the section about login in the appendix. It is only possible to configure one user.
  • Page 44 A.1.14. Update You can update the firmware by means of the built-in webserver. The binary file is supplied by Grundfos. To make installation and configuration easier, you can upload the configuration to a PC for backup or distribution to multiple modules.
  • Page 45 A.1.15. Service info This page gives an overview of the communication status. Service info...
  • Page 46 Appendix B B.1. China RoHS, table C 产品中有害物质的名称及含量 有害物质 部件名称 铅 汞 镉 六价铬 多溴联苯 多溴联苯醚 (Pb) (Hg) (Cd) (Cr6+) (PBB) (PBDE) 印刷电路板 紧固件 本表格依据 SJ/T 11364 的规定编制 O:表示该有害物质在该部件所有均质材料中的含量均在 GB/T 26572 规定的限量要求以下。 X: 表示该有害物质至少在该部件的某一均质材料中的含量超出 GB/T 26572 该规定的限量要求。 该产品环保使用期限为 10 年,标识如左图所示。 此环保期限只适用于产品在安装与使用说明书中所规定的条件下工作...
  • Page 47 Declaration of conformity UK declaration of conformity We, Grundfos, declare under our sole responsibility that the products to which the declaration below relates, are in conformity with UK regulations, standards and specifications to which conformity is declared, as listed below:...
  • Page 48 Grundfos dichiara sotto la sua esclusiva A Grundfos declara sob sua única responsabilidade responsabilità che il prodotto CIM 500, al quale si que o produto CIM 500, ao qual diz respeito a riferisce questa dichiarazione, è conforme alle declaração abaixo, está em conformidade com as seguenti direttive del Consiglio riguardanti il Directivas do Conselho sobre a aproximação das...
  • Page 49 • RoHS Directive (2011/65/EU and 2015/863/EU Standard used: - EN IEC 63000:2018 This EU declaration of conformity is only valid when published as part of the Grundfos installation and operating instructions (publication number 98407037). Bjerringbro, 31 December 2020 Dorte Jepsen...
  • Page 50 Часть 3: информация о сроке изготовления, размещенная на фирменной табличке изделия. Сведения о подтверждении соответствия: Модули передачи данных CIM 500 прошли процедуру подтверждения на соответствие требованиям Технических регламентов Таможенного союза: ТР ТС 004/2011 «О безопасности низковольтного оборудования»; ТР ТС 020/2011 «Электромагнитная совместимость технических средств».
  • Page 51 Մաս 3. տեղեկություն արտադրման ամսաթվի վերաբերյալ՝ նշված սարքավորման պիտակի վրա: Համապատասխանության մասին հայտարարության տեղեկություններ՝ CIM 500 տվյալների փոխանցման մոդուլները անցան հաստատման կարգը `Մաքսային միության տեխնիկական կանոնակարգի պահանջներին համապատասխան. TR TS 004/2011« voltageածր լարման սարքավորումների անվտանգության մասին »; TR TS 020/2011 «Տեխնիկական միջոցների...
  • Page 52 Argentina China Greece Bombas GRUNDFOS de Argentina S.A. GRUNDFOS Pumps (Shanghai) Co. Ltd. GRUNDFOS Hellas A.E.B.E. Ruta Panamericana km. 37.500industin 10F The Hub, No. 33 Suhong Road 20th km. Athinon-Markopoulou Av. 1619 - Garín Pcia. de B.A. Minhang District P.O. Box 71 Tel.: +54-3327 414 444...
  • Page 53 Fax: +66-2-725 8998 Fax: + 370 52 395 431 Москва, RU-109544, Russia Turkey Тел. (+7) 495 564-88-00 (495) 737-30-00 Malaysia GRUNDFOS POMPA San. ve Tic. Ltd. Факс (+7) 495 564 8811 GRUNDFOS Pumps Sdn. Bhd. Sti. E-mail grundfos.moscow@grundfos.com 7 Jalan Peguam U1/25 Gebze Organize Sanayi Bölgesi...
  • Page 54 98407037 03.2021 ECM 1301230...

Table of Contents