Specifications - Grundfos CIM 300 User Manual

Bacnet for grundfos level control lc 2x1 and lc 2x2
Table of Contents

Advertisement

1.7 Specifications

General data
Ambient humidity
Operating temperature
Storage temperature
GENIbus visual diagnostics
BACnet MS/TP
BACnet connector
BACnet connection type
BACnet wire configuration
Maximum cable length
Recommended cross-section of BACnet cable
MAC address
Line termination
Supported transmission speeds [bit/s]
Data bits
Stop bits
Parity
BACnet visual diagnostics
Maximum number of BACnet devices
Grundfos BACnet vendor ID
BACnet segmentation support
Character set support
BACnet device profile
BACnet MS/TP master
Manual slave address binding
BACnet protocol revision
BACnet IP
Application layer
Transport layer
Internet layer
Link layer
Ethernet cable
Maximum cable length
Transmission speed
Industrial Ethernet protocols
BACnet protocol revision
CIM 300 and 500
Dimensions [w x h x d] [mm]
Power supply
Connection to booster system
Related information
2.2 CIM 300 BACnet module
2.3 Connecting to the BACnet network
2.4 Setting the BACnet transmission speed
2.7 Selecting the BACnet MAC address
2.8 Termination resistor
2.10 LEDs
2.10.1 LED1, BACnet MS/TP communication
3.2 Setting the Industrial Ethernet protocol
Description
30-95 %
-20 to +45 °C
-25 to +70 °C
LED2
Description
Screw-type terminal
RS-485
Two-wire + ground
1200 m
2
0.20 - 0.25 mm
0-127
On or Off
9600, 19200, 38400, 76800
8
1
None
LED1
32
227
No
ANSI X3.4
B-ASC
Yes
No
For hardware version R4: 4
For hardware version R8: 9
Description
DHCP, HTTP, Ping, FTP, SMTP, SNTP,
BACnet IP
UDP
Internet protocol V4 (IPv4)
ARP, media access control (Ethernet)
CAT5, CAT5e or CAT6
100 metres at 10/100 Mbit/s
10 Mbit/s, 100 Mbit/s
PROFINET IO, BACnet IP etc.
9
50 x 19 x 80
10-pin connection
Comments
Relative, non-condensing.
The LED will be in one of these states:
Off, permanently green, flashing red, permanently red.
Comments
3 pins.
Conductors: Plus, Minus and Ground.
Equals 4000 ft
AWG24 or AWG23
Set via rotary switches SW6 and SW7.
Set via DIP switches SW1 and SW2.
Set via DIP switches SW4 and SW5.
Fixed value
Fixed value
Fixed value
Red and green status LED.
Using repeaters, this number can be increased.
Base definition for the widely used character code known as
ASCII.
BACnet Application-Specific controller
CIM/CIU 300 and 500 are BACnet MS/TP master devices.
Comments
Rotary switch in position 2.
Supports auto cable-crossover detecting (Auto-MDIX).
Corresponds to 328 feet.
Auto-detected
Selected with rotary switch.
Supplied by the LC 2XX controller.