Analog Inputs - Grundfos CIM 300 User Manual

Bacnet for grundfos level control lc 2x1 and lc 2x2
Table of Contents

Advertisement

5.6 Analog inputs

Objects with measured values and status information from the pump
ID
Object name
AI, 0
Fault code
AI, 1
Warning code
AI, 2
HighLevel
AI, 3
StartLevelPump1
AI, 4
StopLevelPump1
AI, 5
StartLevelPump2
AI, 6
Pit water level
AI, 7
Pit power consumption
AI, 8
Pit energy consumption
AI, 9
Pit running time
AI, 10
Analog Input 1 (AI1)
AI, 11
Analog Input 2 (AI2)
AI, 12
Analog Input 3 (AI3)
AI, 13
Pump1 time to service
AI, 14
Pump2 time to service
AI, 15
Pump1 start counter
AI, 16
Pump2 start counter
AI, 17
Pump1 current
AI, 18
Pump2 current
AI, 19
Pump1 operating time
AI, 20
Pump2 operating time
AI, 21
UserAnalogInput1
AI, 22
UserAnalogInput2
AI, 23
UserAnalogInput3
AI, 24
UserAnalogInput4
AI, 25
UserAnalogInput5
AI, 26
Last operating time pump1
AI, 27
Last operating time pump2
AI, 28
Energy consumption pump1
AI, 29
Energy consumption pump2
AI, 30
System Energy today
AI, 31
PulseFlowMeter
AI, 32
Turbidity
AI, 33
PhMeasure
AI, 34
Conductivity
AI, 35
Pump1OprTimeToday
AI, 36
Pump2OprTimeToday
AI, 37
Pump1StartCounterToday
AI, 38
Pump2StartCounterToday
AI, 39
Alarms 1-5 and warnings 1-5
18
R/W
Description
R
Grundfos fault code.
R
Grundfos warning code.
R
High level in centimetres.
R
Start level for pump 1 in centimetres.
R
Stop level for pump 1 in centimetres.
R
Start level for pump 2 in centimetres.
R
Pit water level in centimetres.
R
Pit power consumption in watts.
R
Pit energy consumption in kilowatt hours.
R
Pit running time in minutes.
R
Analog Input 1
R
Analog Input 2
R
Analog Input 3
R
Pump 1 time to service in minutes.
R
Pump 2 time to service in minutes.
R
Pump 1 start counter.
R
Pump 2 start counter.
R
Pump 1 current in amperes.
R
Pump 2 current in amperes.
R
Pump 1 overall operating time in minutes.
R
Pump 2 overall operating time in minutes.
R
User-defined measurement, analog input 1.
R
User-defined measurement, analog input 2.
R
User-defined measurement, analog input 3.
R
User-defined measurement, analog input 4.
R
User-defined measurement, analog input 5.
R
Last operating time for pump 1.
R
Last operating time for pump 2.
R
Energy consumption pump 1.
R
Energy consumption pump 2.
R
DATA_ENERGY_TODAY reported with 0.1 kWh resolution.
R
DATA_PULSE_FLOW_METER
R
DATA_TURBIDITY reported with 0.1 NTU resolution.
R
DATA_PH_MEASURE reported with 0.1 pH resolution.
R
DATA_CONDUCTIVITY reported with 1 S/m resolution.
R
DATA_PUMP1_RUNTIME_TODAY
R
DATA_PUMP2_RUNTIME_TODAY
R
DATA_PUMP1_RUNTIME_TODAY
R
DATA_PUMP2_RUNTIME_TODAY
Values are transmitted in the following order:
bit 0: Status warning 1
bit 1: Status warning 2
bit 2: Status warning 3
bit 3: Status warning 4
bit 4: Status warning 5
bit 8: Status alarm 1
R
bit 9: Status alarm 2
bit 10: Status alarm 3
bit 11: Status alarm 4
bit 12: Status alarm 5
Bit values indicate the following:
bit value 0: Alarm or warning not present
bit value 1: Alarm or warning present
Unit
LC 2X1
LC 2X2
-
-
cm
cm
cm
cm
cm
W
kWh
min
%
%
%
min
min
-
-
A
A
min
min
%
%
%
%
%
s
s
kWh
kWh
kWh
-
l/s
NTU
pH
S/m
min
-
min
-
min
-
min
-
-