9. BACnet telegrams

9.1 BACnet MS/TP telegram overview

All BACnet MS/TP telegrams have the following format:
Preamble
Telegram type
2 bytes:
1 byte
0x55 0xFF
For BACnet MS/TP, the destination address and source address are MAC addresses. A destination address of 255 (0xFF) denotes broadcast.
The length field specifies the length in bytes of the data field which must be between 0 and 501 bytes long.
Related information
2.7 Selecting the BACnet MAC address

9.2 Telegram types

The available telegram types are listed below.
Type
Name
00
Token
01
Poll for master
02
Reply to poll for master
03
Test request
04
Test response
05
BACnet data, expecting reply
06
BACnet data, not expecting reply
07
Reply postponed
Destination
Source
Length
2 bytes, MSB
1 byte
1 byte
Description
Used to pass network mastership to the destination device.
Discovers the presence of other master devices on the network.
Used by a master to indicate a wish to enter the token ring.
Used to initiate a loopback test.
A reply to a test request telegram.
Used for data transmission where a reply is expected.
Used for data transmission where no reply is expected.
Used by master devices to defer sending a BACnet data reply.
Header CRC
Data
Variable,
1 byte
first
[0-501] bytes
Data CRC
Pad
2 bytes, LSB
At most 1 byte 0xFF
first