Powering On and Off the System

17
5. Powering On and Off the System

5.1. Powering on the System

1) Switch on the battery breaker of the batteries.
2) Switch on the battery breaker which is at the bottom of the SMILE-G3-INV.
3) Press the battery button, if there are more than one battery, the button for each
battery should be pressed within 5s of the previous one.
4) Switch on the AC breaker between the grid port of the SMILE-G3-INV and the grid.
5) Switch on the AC breaker between the backup port of the SMILE-G3-INV and the
loads.
6) Switch on the PV switch at the bottom of the SMILE-G3-INV if there is any.
7) Switch on the AC breaker (if there is any) between the PV-inverter and the grid.

5.2. Powering off the System

After the energy storage system is powered off, the remaining electricity and heat
may still cause electric shocks and body burns. Therefore, put on protective gloves
and operate the product 5 minutes after the power-off.
Procedure
1) Switch off the AC breaker between the SMILE-G3-INV and the load.
2) Switch off the AC breaker between the SMILE-G3-INV and the grid.
3) Switch off the PV switch at the bottom of the SMILE-G3-INV if there is any.
4) Switch off the PV switch between the PV string and the SMILE-G3-INV if there is
any.
5) Switch off the battery breaker which is at the bottom of the SMILE-G3-INV.
6) Long press 5s the power button of the battery.
7) Switch off the battery breaker of the battery.