Mounting The Measuring Device - Endress+Hauser Liquiphant FTL41 Brief Operating Instructions

Vibronic point level switch in liquids
Hide thumbs Also See for Liquiphant FTL41:
Table of Contents

Advertisement

Liquiphant FTL41
4.2

Mounting the measuring device

4.2.1
Required tools
Open-ended wrench, Allen key
4.2.2
Installation
Horizontal installation in vessels
Align the tuning fork with the marking
316L/G1
 11
Markings to align the tuning fork
Use the marking to align the tuning fork in such a way that medium can run off easily and
deposit buildup is avoided.
Markings may include the following:
• Material specification, thread description or circle on the hexagonal nut or on the weld-in
adapter
• The II symbol on the back of the flange or Tri-Clamp
Installing in pipes
• Flow velocities up to 5 m/s at a viscosity of 1 mm
Check for correct functioning in the event of other process medium conditions.
• The flow will not be significantly impeded if the tuning fork is correctly aligned and the
marking is pointing in the direction of flow.
• The marking can be identified while the device is installed
Endress+Hauser
2
/s(cSt) and density 1 g/cm
Mounting
A0039125
3
(SGU)
13