Automatic settings and auto area learn

Execute the following with the function switch on the OA-607 T front or with the setting app.
Auto configuration:
ELITE PRO has an advance learning system that can recognize the following system configuration and status and set the related parameters
properly and automatically for easy and quick settings.
After parameter settings, it automatically starts auto area learn to setup the area for each OA sensor heads to complete auto configuration.
● Test input (Enable or Disable)
● Test input polarity (High or Low)
● Stall output (N.O. or N.C.)
● Sensor side (Approach or Swing side)
● Hinge side (Right Hand or Left hand)
Auto area learn:
OA has a learning system that check the condition of floor surface for door opening angles.
„ OA-607 T function switch operation
WARNING
WARNING
The door opens and closes automatically, so move away from it after starting.
Procedure
Conditions
Operation
for opera-
tion
During initial
Door fully
Hold down the front
setup
closed
function switch
(more than 2 s)
When
None in
Briefly press the
adjusting
particular
front function switch
the angle
(more than 0.3 s, no
or changing
more than 2 s) once
the settings
after auto
configura-
tion
*1: Twice or three times in accordance with the door controller signal input setting (combination of stall signal and test signal, etc.) during auto configuration.
NOTE
NOTE
Before executing auto configuration, the connection between the door controller and the OC-907C T sensor controller must be complete.
Auto configuration must be started with the door fully closed. Otherwise, a setting error will be generated.
18
Press front function switch
Result
Operation
Auto configuration start
Execute auto configuration
The door will open and close two or
three times automatically (*1).
Upon failure, after checking the wir-
ing, execute auto configuration again.
If there is no problem with the wiring,
manual setting from a smart device is
also possible.
After installation is complete, leave
the power on for at least 30 minutes
in order to achieve stable operation
during use.
Start auto area learn only
Execute auto area learn only
Other
Check in advance that the door is fully closed.
Indicator
OA-607 T operation indicator
Blinking fast in Orange (0.1 s intervals) = Auto configuration
start
Solid Green after normal completion
= Setup complete (stand-by)
Upon failure:
Blinking Orange (0.5 s intervals)
(= Setting error)
Blinking fast in Yellow (0.1 s intervals) = Start auto area learn only
Solid Green after normal completion = Setup complete (stand-by)
If the door is prevented from opening by an obstacle or the
power is cut just after auto area learn is complete: blinking
alternately Yellow and Red (0.1 s intervals) = Incomplete
OC-907C T operation indicator