3.3.1
Connector J1 outputs 5...10
Connector J1 will be assembled in the presence of auxiliary outputs (O5...O8).
Figure 11
Connector J1
OUTPUTS 5...8 Logical (option D) / Analogue (option W)
Logic outputs:
18...36Vdc, max 20mA
Continuous outputs: voltage (default) 0/2...10V, max 25mA
current 0/4...20mA, max 500Ω
Figure 12
Wiring diagram for logical/analogue outputs
I
+
+
+
+
V
RELAY OUTPUTS 5...8 (option R)
Outputs Out 5...8 relay Ir = 3A max, NO
V = 250V/30Vdc cosφ = 1; I = 12A max
Figure 13
Connection scheme for relay outputs
I
V
18
2
O5
3
O6
4
O7
5
O8
1
Com 5¸8
1
Com 5¸8
2
Ir
O5
3
O6
4
O7
5
O8
Table 6
Table 7
PIN
Name
1
Com 5-8
Outputs common
2
O5
3
O6
4
O7
5
O8
Table 8
PIN
Name
1
Com 5-8
2
O5
3
O6
4
O7
5
O8
80999D_MHW_GFW 400-600A_07-2020_ENG
0.25 - 2.5mm2
23-14AWG
0.25 - 2.5mm2
23-14AWG
Decription
Logic
Analogue
(-)
Output 5
(+)
Output 6
(+)
Output 7
(+)
Output 8
(n.c.)
Decription
Common outputs
Output 5
Output 6
Output 7
Output 8