Drive parameter
20.40 Run permissive
20.01 Ext1 commands/
20.06 Ext2 commands
20.41 Start interlock 1
20.42 Start interlock 2
Relay output control
■
For relay output control through BACnet/IP:
•
set the following drive parameters to select the source for the relay outputs
•
set the drive for control through BACnet
•
set the building controller supplied binary coded relay command(s) in the
appropriate location.
Drive parameter
10.24 RO1 source
10.27 RO2 source
10.30 RO3 source
15.07 RO4 source
15.10 RO5 source
15.23 DO1 source
Data point connections
The BACnet access points of the above relay output control parameters are in turn
linked to the following parameters:
BACnet access point
BO0...BO5
Analog output control
■
For analog output control through BACnet/IP, configure the following drive parameters
and set the fieldbus controller supplied analog value(s) in the appropriate location.
Value
Description
Fieldbus adapter
Run permission by field-
bus
Fieldbus A
Fault reset by fieldbus
Fieldbus adapter
Source for start interlock
1 is fieldbus
Fieldbus adapter
Source for start interlock
2 is fieldbus
Value
Description
RO/DIO control word
Relay output 1 controlled
bit0
by fieldbus
RO/DIO control word
Relay output 2 controlled
bit1
by fieldbus
RO/DIO control word
Relay output 3 controlled
bit2
by fieldbus
RO/DIO control word
Relay output 4 controlled
bit3
by fieldbus
RO/DIO control word
Relay output 5 controlled
bit4
by fieldbus
RO/DIO control word
Digital output 1 con-
bit8
trolled by fieldbus
Drive parameter
10.99 RO/DIO control word
Start-up 31
BACnet access point
BV12
BV14
BV20
BV21
BACnet access point
BO0
BO1
BO2
BO3
BO4
12
BO5
Description
Storage parameter for
relay output and digital
outputs