26 Start-up
No.
Name/Value
Description
14
Device obj ID lo
Defines the device object ID for BACnet devices. The Device Object
ID needs to be unique across all BACnet devices in the building net-
work. Valid values are 0...4194303.
For values 0...9999, this parameter sets the values directly. For values
greater than 9999, the ID is calculated with this formula: Device ID =
(10000 * par. 15) + par. 14.
0...9999
Device ID
15
Device obj ID hi
Defines the device object ID for BACnet devices.
0...419
Device ID
16
Max APDU re-
Defines the number of retries to send when no response is seen to
tries
confirmed requests.
0...10
Number of retries.
17
APDU timeout
Defines the time a client waits for response from a BACnet device.
6...60 s
Waiting time.
18
BACnet/IP port
Sets the UDP port used for the BACnet/IP communication. By default
port 0xBAC0/47808 is used.
20
Timeout time
Sets the delay time for directing messages to the drive before a
communication loss condition is declared.
• If value is zero, the feature is disabled.
• If value is non zero, the timeout is in units of 100ms. For example,
0...65535
Delay time
21
Timeout mode
Defines the message type that resets the timeout counter for detect-
ing communication loss between the drive and the master.
1 = Any packet
Any message directed to the drive resets the timeout.
2 =Control RW
A write to control or reference resets the timeout.
a value of 300 is 30.0 seconds.
Default
0
0
3
6 s
0xBAC0
(47808)
300
(30.0 s)
1 = Any
packet