24 Start-up
No.
Name/Value
Description
01
FBA type
Shows the fieldbus adapter type as detected by the drive. You cannot
adjust this value.
This parameter is read-only.
0 = None
Communication between the drive and the module is not established.
47808 = BACnet
BACnet
02
Reserved
This parameter is not used by the adapter module.
03
Commrate
Sets the bit rate of the communication and determines if the commu-
nication can be simultaneously two-way (full duplex) or only one way
(half duplex).
0 = Auto
Auto-negotiate
1 = 100 Mbps FD
100 Mbps, full duplex
2 = 100 Mbps
100 Mbps, half duplex
HD
3 = 10 Mbps FD
10 Mbps, full duplex
4 = 10 Mbps HD
10 Mbps, half duplex
04
IP configuration
Sets the method for configuring the IP address, subnet mask and
gateway address for the Ethernet interface.
0 = Static IP
Configuration will be obtained from parameters 05...13.
1 = Dyn IP DHCP
Configuration is obtained via DHCP.
05
IP address 1
An IP address is assigned to each IP node on a network. An IP address
is a 32-bit number that is typically represented in "dotted decimal"
notation consisting of four decimal integers, in the range 0...255,
separated by periods. Each integer represents the value of one octet
(8- bits) in the IP address. Parameters 05...08 define the four octets
of the IP address.
0...255
IP address
...
...
...
08
IP address 4
See parameter 05 IP address 1.
0...255
IP address
Default
47808 =
BACnet
-
0 = Auto
1 = Dyn
IP DHCP
0
...
0