ABB FBIP-21 BACnet/IP User Manual page 37

Adapter module
Table of Contents

Advertisement

Drive parameter
51.05 IP address 1
51.06 IP address 2
51.07 IP address 3
51.08 IP address 4
51.09 Subnet CIDR
51.14 Device obj ID lo
51.20 Comm loss time
51.21 Comm loss mode
51.27 FBA A par refresh
20.01 Ext1 commands
28.11 Ext1 frequency ref1
1) Read-only or automatically detected/set
2) Example
Settings
2)
192
2)
168
2)
0
2)
16
2)
24
2)
51
2)
300
2)
1 = Any message
1 = Configure
12 = Fieldbus A
4 = FB A ref1
Start-up 37
Description
First part of the IP address
Second part of the IP address
Third part of the IP address
Last part of the IP address
Sets the network mask as
255.255.255.0, allowing access
only to the last subnet.
Configures device object ID.
Sets the communication timeout
as 30 seconds.
The timeout feature monitors the
updating of the Control word and
Reference 1.
Validates the FBIP-21 configura-
tion parameter settings.
Selects the Fieldbus A interface
as the source of start and stop
commands for external control
location 1.
Selects fieldbus reference 1 as the
source for frequency reference 1.
12