Binary Value Object - ABB FBIP-21 BACnet/IP User Manual

Adapter module
Table of Contents

Advertisement

Binary value object

Object
Default object name
ID
BV0
RUN-STOP-Monitor
BV1
Direction-Monitor
BV2
OK-FAULT-Monitor
BV3
EXT1-EXT2-Monitor
BV4
HAND-AUTO-Monitor
BV5
Warning-Monitor
BV7
Ready-Monitor
BV8
At-Setpoint-Monitor
BV9
Enabled-Monitor
BV10
RUN-STOP-Command
BV11
Direction-Command
BV12
Run- Permissive-Com-
mand
BV13
EXT1-EXT2-Command
BV14
Fault-Reset-Command
BV17
Lock-Parameters
BV18
Control- Override-
Command
Description
Run status of drive
Rotational direction of
the motor
Actual fault status of
drive
Actual control source
Actual operating
mode
Actual warning status
Actual ready status
Actual at setpoint
status
Actual run enabled
status
Command to start
drive
Command to rotation-
al direction
Command to Run Per-
missive command
Command to External
1 or External 2
Command to fault re-
set
Actual status of para-
meter lock.
Command the drive
into BACnet Control
Override. In this mode
BACnet acquires drive
control from its nor-
mal source.
Note: The HAND mode
of the panel has prior-
ity over BACnet Con-
trol Override.
Communication protocol 45
Default active/ Inact-
ive text
RUN / STOP
REVERSE / FORWARD
FAULT / OK
EXT2 / EXT1
HAND / AUTO
WARNING / OK
READY / NOT- READY
YES / NO
ENABLE / DISABLE
RUN / STOP
REVERSE / FORWARD
ENABLE / DISABLE
EXT2 / EXT1
RESET / NO
LOCK / UNLOCK
ON / OFF
Present value access
type
R
R
R
R
R
R
R
R
R
C
C
C
C
W
R
C

Advertisement