40 Communication protocol
BACnet interoperability building blocks
The following BACnet interoperability building blocks that is collection of one or more
services, are supported by FBIP-21:
Building block
Description
(short name)
DS-COV-B
Data Sharing – Change of Value
DS-RP-B
Data Sharing – Read Property – B (Provider / Server)
DS-RPM-B
Data Sharing – Read Property Multiple – B (Provider / Server)
DS-WP-B
Data Sharing – Write Property – B (Provider / Server)
DS-WPM-B
Data Sharing – Write Property Multiple – B (Provider / Server)
DM-DDB-B
Device Management – Dynamic Device Binding – B (Provider / Server)
DM-DOB-B
Device Management – Dynamic Object Binding – B (Provider / Server)
DM-DCC-B
Device Management – Device Communication Control – B (Provider / Server), password
is not required
DM-RD-B
Device Management – Reinitialize Device B (Provider / Server), password is not required
DM-TS-B
Device Management – Time Synchronization
BACnet object list
The adapter module supports the BACnet objects listed below. The present value
property of the object can be readable (R), writable (W) or commandable (C), i.e.
writable with priority.
During the first boot, the FBIP-21 will build a BACnet object list based on the available
functionalities in the connected drive. Note that the objects listed below are not
available for all drives.
Analog input object
■
Object
Default object
ID
name
AI0
AI1-Monitor
AI1
AI2-Monitor
Analog output object
■
Object
Default object
ID
name
AO0
AO1-command
Description
Indicates the input level of analog input
1.
Indicates the input level of analog input
2.
Description
Controls analog output 1 (drive must be
configured for BACnet control).
Minim-
Unit
Present
um/Maxim-
value ac-
um preset
cess type
value
0,100
%
R
0,100
%
R
Minimum/
Unit
Present
Maximum
value ac-
preset
cess type
value
0,100
%
C