34 Start-up
Drive parameter
01.01 Motor speed used
01.06 Output frequency
01.11 DC voltage
01.13 Output voltage
01.07 Motor current
01.10 Motor torque
01.14 Output power
05.11 Inverter temperature
01.57 Inverter kWh counter (reset-
table)
01.20 Inverter kWh counter
40.97 Process PID feedback %
40.99 Process PID deviation %
-
-
35.01 Motor estimated temperat-
ure
01.03 Motor speed %
01.50 Current hour kWh
Description
Estimated motor speed in RPM
Estimated drive output frequency
in Hz
DC bus voltage
Calculated motor voltage in V AC
Measured (absolute) motor cur-
rent in A
Motor torque in percent of the
nominal motor torque
Drive output power
Estimated drive temperature in
percent of fault limit
Cumulative energy usage of the
drive. This value can be reset.
Amount of energy that has
passed through the drive (in
either direction) in full kilowat-
thours. Whenever the counter
rolls over, 01.19 Inverter MWh
counter is incremented. The min-
imum value is zero.
This object is the Process PID
feedback signal.
This object is the Process PID
output signal's deviation from its
setpoint.
External PID feedback percentage
scaled
This object is the External PID
output signal's deviation from its
setpoint.
Displays the motor temperature
as estimated by the internal mo-
tor thermal protection model
Motor speed in percent of the
synchronous motor speed.
Current hour energy consump-
tion. This is the energy of the last
60 minutes (not necessarily con-
tinuous) the drive has been run-
ning, not the energy of a calendar
hour. The value is set to the value
before the power cycle when the
drive is again up and running.
BACnet access point
AV0
AV1
AV2
AV3
AV4
AV5
AV6
AV7
AV8
AV9
AV10
AV11
AV12
AV13
AV15
AV31
AV130