Start-Up; Contents Of This Chapter; Configuring The Bacnet/Ip Connection; Fbip-21 Configuration Parameters - Group A (Group 1) - ABB FBIP-21 BACnet/IP User Manual

Adapter module
Table of Contents

Advertisement

Start-up

Contents of this chapter

This chapter contains:
information on configuring the drive for operation with the adapter module
drive-specific instructions on starting up the drive with the adapter module
information on configuring the client for communication with the adapter module.

Configuring the BACnet/IP connection

After the adapter module has been mechanically and electrically installed according
to the instructions in chapters
installation (page
21), you must prepare the drive for communication with the module.
The detailed procedure for activating the module for BACnet/IP communication with
the drive depends on the drive type. Normally, you must adjust a parameter to activate
the communication. See
ACH580 drives (page
36).
Once communication between the drive and the adapter module has been established,
several configuration parameters are copied to the adapter module. These parameters
are shown in the tables below and must be checked first and adjusted where necessary.
You can adjust the parameters via a drive control panel or a PC tool.
Note: The new parameter settings take effect only when you power up the module
the next time or when you activate the fieldbus adapter refresh parameter.
FBIP-21 configuration parameters – group A (group 1)
Group A (group 1) corresponds to parameter group 51 in the drive.
Mechanical installation (page 19)
Starting up BACnet/IP communication for ACH480 and
Start-up 23
6
12
and
Electrical

Advertisement

Table of Contents
loading

Table of Contents