No.
Name/Value
Description
22
Service configur-
Disable services that are not required. Each service is represented
ation
by a single bit. Bit 0, Lock configuration, can be used to prevent acci-
dental changing of this parameter. By default, all services are enabled
and configuration is unlocked.
Bit
0
1
2
3
4
5
23
Reserved
...
26
27
FBA Par refresh
Validates any changed adapter module configuration parameter
settings. After refreshing, the value reverts automatically to Done.
This parameter cannot be changed while the drive is running.
0 = Done
Refreshing done
1 = Configure
Refreshing
28
FBA Par table
Displays the parameter table revision of the fieldbus adapter module
ver
mapping file stored in the memory of the drive.
In format xyz, where
x = major revision number
y = minor revision number
z = correction number
This parameter is read-only.
0..0xFFFF
Parameter table revision
29
FBA Drive type
Displays the drive type code of the fieldbus adapter module mapping
code
file stored in the memory of the drive.
This parameter is read-only.
Name
Information
Lock configura-
Changing this bit to one will lock service
tion
configuration and no bit can be changed.
Only resetting the fieldbus configuration
will unlock the parameter. To reset the
fieldbus configuration, choose "Reset all
fieldbus settings" or "Clear all" in parameter
96.06 Parameter restore.
Disable IP con-
When this bit is set, access from ABB IP
fig tool
Configuration tool is prevented.
Disable ETH
When this bit is set, access from Ethernet
tool network
tool network (eg, ABB Drive Composer tool)
is prevented.
Disable ping re-
When this bit is set, response to ICMP (ping)
sponse
message is prevented.
Unsecured ETH
When this bit is set, access from Ethernet
tool network
tool network is unsecured.
Note: Drive Composer pro before V2.7 sup-
ports unsecured communication only.
Disable config-
When this bit is set, access to web pages
uring web
is disabled.
pages
Start-up 27
Default
12
0 = Done
0 hex