I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N
Bypass-Isolation Automatic
Transfer Switches
Zenith ZBTS T-series, 100 - 1200 A

Advertisement

Table of Contents
loading

Summary of Contents for ABB Zenith ZBTS T Series

  • Page 1 I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Bypass-Isolation Automatic Transfer Switches Zenith ZBTS T-series, 100 - 1200 A...
  • Page 2 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
  • Page 3 HAZARD OF EQUIPMENT with the transportation company, and no- OVERTURNING tify your local ABB sales office. When moving with a fork lift, do not re- move the shipping package until the de- Do not remove the shipping package until ready to install the Bypass-Isolation Auto- vice is in its final location.
  • Page 4 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — Read these safety instructions carefully before using this product! Danger Warning...
  • Page 5 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — Installation and Operating Instruction OPER ATING INSTRUCTIONS, Bypass-Isolation ZENITH ZBTS T-SERIES...
  • Page 6 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
  • Page 7: Table Of Contents

    3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — Operating Instruction Bypass-Isolation Automatic Transfer Switches, Zenith ZBTS T-series 100-1200A PART 1...
  • Page 8 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 3.3 HMI, menu tree 3.3.1 Start Menu 3.4 Description of Basic Functionality 3.4.1 How to draw out the switch to Test...
  • Page 9 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 6. Technical Data 6.1 Technical Data of Bypass-Isolation Transfer Switches 6.1.1 I/O Contacts, Default Settings / Bypass-Isolation Automatic...
  • Page 10 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
  • Page 11: Introduction

    1. Introduction Operating instruction part of the manual The safe operation of your Bypass-Isola- (Chapters 1...6) describes the basic oper- tion Automatic Transfer Switch is ABB’s ation of the Bypass-isolation automatic focus. The proper storage, installation, transfer switches Zenith ZBTS T-series operation and maintenance will help in- 100-1200A, manufactured by ABB.
  • Page 12: Warranty

    ABB representative for Non-US war- hardware and software systems. ranty terms and conditions. ABB Zenith assumes no obligation of no- For support in the United States, contact tice to holders of this document with re- service team at: +1 800 637 1738 or spect to changes subsequently made.
  • Page 13: Product Specification

    Strict procedures ensure firstclass product quality. Product Rating / Applicable Standards For UL 1008 ‘withstand’ and ‘close on short circuit’ ratings, refer to ABB publica- tion number 1SCC303020C0201. Product Serial Number Please have the serial number available when communicating about the By- pass-Isolation automatic transfer switch.
  • Page 14: Definitions

    Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 1.4 Definitions Automatic transfer switches Source 1, relate to a Normal Power Source Ekip Electronic accessories / Ekip-modules;...
  • Page 15: Product Overview

    ATS is disabled or removed from service. Bypass-Isolation Automatic Transfer Switch, consist of two ABB Zenith Auto- matic Transfer Switches (TruONE ATS) from 100A up to 1200A, are used to pro- vide a continuous source of power for critical loads.
  • Page 16 The ATS Warning Due to hazardous voltage and current, ABB switch in the lower switch module is al- recommends that ABB certified technician or ways a draw-out version that includes an qualified electrician perform the installation and maintenance.
  • Page 17: General Overview

    3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 2.1 General Overview 4 3 2 Ground Terminal Fixed Bypass in the picture (alternative: Bypass is draw-out...
  • Page 18 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Operation instruction HMI unit on the door, Level 4 (touch) for configuration and automatic operation, operation of the Bypass switch...
  • Page 19: Main And Control Connections

    3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 2.2 Main and Control Connections 2.2.1 Main Connections The top module of enclosure is for cable lugs for Source 1, for Source 2 and for...
  • Page 20: Interlocks

    Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N The upper switch is the Bypass switch. It can be fixed or draw-out version.
  • Page 21: Hmi

    3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 2.3 HMI HMIs are the control interfaces (Human touch screen for both switches Bypass Machine Interface), available as level 4 for and ATS.
  • Page 22: Bypass And Ats Switches, Features

    Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 2.4 Bypass and ATS Switches, Features Features Level 4 controls (TOUCH) LOAD...
  • Page 23 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 Features Level 4 controls (TOUCH) LOAD AUTO Override momentary...
  • Page 24 For applications Mains - Mains Mains - Generator Contact ABB for applications with smaller than 20 kVA gensets Includes support for redundant module — Table 2.1 ATS feature comparison, main features - but not limited to - in the table above...
  • Page 25: Operating

    3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 3. Operating — 3.1 LED Functionality in HMIs LED functionality in HMIs is similiar for both Bypass and ATS switches.
  • Page 26 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Bypass Lamp Auto load load time test...
  • Page 27: Using The Control Interface Hmi

    3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 3.2 Using the Control Interface HMI 3.2.1 Keypad Keypad functionality in HMIs is similiar for both Bypass and ATS switches...
  • Page 28: Hmi, Menu Tree

    Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 3.3 HMI, menu tree Password The small icons in Switch Overview -pages are:...
  • Page 29 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 Alarm List To Define the Home Page 11:06 Alarm List Switch Overview...
  • Page 30: Start Menu

    Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 3.3.1 Start Menu Overviews Analog Meters Switch Overview —...
  • Page 31 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 3.3.1.2 Bypass System Overview 10:55 Bypass System Overview LOAD AUTO...
  • Page 32 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 3.3.1.3 Main Menu Overviews Analog Meters Overviews Switch Overview...
  • Page 33 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 Operation *Default Alarm Reset Reset any active switch control alarms (open I failure, close I failure, open II failure, close II failure) Bypass Time Delay Bypass any currently running time delay...
  • Page 34 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 3.3.1.4 Analog Meters Overviews Analog Meters Switch Overview 0.0V...
  • Page 35: Description Of Basic Functionality

    3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 3.4 Description of Basic Functionality The system provides the ability to with- tion allows also the use of the HMIs on draw the ATS for test and / or mainte-...
  • Page 36: How To Use The Draw-Out

    Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Warning ATS and Bypass switch "OFF" Position keys are always enabled.
  • Page 37 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 The switch and HMI of ATS has now lost 00:34 the power, the ATS is completely discon- Switch Overview...
  • Page 38: Mechanism To Rack Out The Switch

    Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 3.4.2 How to use the Draw-out 05:11 Mechanism to rack out the Switch Switch Overview...
  • Page 39 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 NOTE! In Test location all electrical opera- While the ATS is racked out to the Test lo- tions are allowed.
  • Page 40 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N In CONNECTED location In CONNECTED location, Push button pushed, Push button returns, TEST location reached, Racking in/out tool inserted, ready to start rotation Push button pushed agen, Racking in/out tool...
  • Page 41 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 HMI of Bypass: HMI of ATS: Page “Bypass System Overview”...
  • Page 42: To Reconnect Ats Switch

    Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 3.4.3 To Reconnect ATS Switch NOTE! Remember that ATS must be in Reconnecting the ATS switch after main- OFF-position, when moving in/out.
  • Page 43 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 Operate Bypass switch to OFF- 00:14 position as shown in the Fig.
  • Page 44 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
  • Page 45: Electronic Accessories

    3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 4. Electronic Accessories NOTE! It is still possible to add two pieces of Ekip modules to the fixed Bypass switch Warning Hazardous voltage may be present within the...
  • Page 46: Auxiliary Power Supply Module Oxea1

    Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 4.1 Auxiliary Power Supply Module OXEA1 The auxiliary power supply module, type ferrule;...
  • Page 47: Ekip Supply Module

    3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 4.2 Ekip Supply Module The Ekip Supply is a power supply acces- 4.2.2 Signallings sory module.
  • Page 48: Ekip Signalling 2K -Module

    Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 4.3 Ekip Signalling 2K -module The Ekip Signalling 2K-3 is a signalling ac- Component Characteristics...
  • Page 49 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 Settings (*Default) Description Modules (Optional modules) Ekip Signalling 2K -3 I 11/12, I 21/22, I 31/32...
  • Page 50 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Settings (*Default) Description Modules (Optional modules) (continued) O 11/12, O 21/22, O 31/32 Function* Function No...
  • Page 51 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 Test Modules (Optional modules) Ekip Signalling 2K-1 / -2 / Auto Test —...
  • Page 52: Signals And Inputs/Outputs Of Ekip Signalling 2K -Module

    Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 4.3.3 Signals and inputs/outputs of Green LED for signalling the physical Ekip Signalling 2K -module...
  • Page 53: Troubleshooting

    3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 5. Troubleshooting Warning Danger Any troubleshooting should be conducted by Hazardous voltage may be present.
  • Page 54 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Alarms, continued from previous page Message Fault Action...
  • Page 55 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 Alarms, continued from previous page Message Fault Action...
  • Page 56: Warnings

    Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 5.2 Warnings Message Reason S1 and S2 not in sync Voltage sources are not synchronized...
  • Page 57: Information

    3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 5.3 Information Message Description Invalid Date Date not set Test on Load...
  • Page 58 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
  • Page 59 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 6. Technical Data 6.1 Technical Data of Bypass-Isolation Transfer Switches Bypass-Isolation Transfer Switch, Power Circuit Value Rated operational voltage U, three phase...
  • Page 60 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Automatic Transfer Switch, I/O Contacts Cabling Rating / Remark Generator start/stop...
  • Page 61 Table 6.4 Automatic transfer switches: Specified technical data of operating times Type peak 500 V [kA] 100...1200 Iq 100 kA rms. OFA_1600 A gG 80.8 9900 OFA_1250 A aM 91.3 11600 Iq 85 kA rms. ABB T7L1600_ 111.6 44900 — Table 6.5 Automatic transfer switches: Rated conditional short-circuit values...
  • Page 62 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 6.1.1 I/O Contacts, Default Settings / Bypass-Isolation Automatic Transfer Switch These settings are for internal use only, these settings cannot be changed.
  • Page 63 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 6.2 Circuit Diagrams The following pages contain simplified circuit diagrams for Bypass-Isolation au- tomatic transfer switch products.
  • Page 64 Pidätämme itsellemme kaikki oikeudet tähän asiakirjaan ja siihen liittyvään informaatioon. Reproduction, use or disclosure to third parties without express authority is Asiakirjan toisintaminen, käyttö tai sen sisällön paljastaminen kolmannelle osapuolelle strictly forbidden. © Copyright 2019 ABB. ilman nimenomaista suostumustamme on ehdottomasti kielletty. © Copyright 2019 ABB.
  • Page 65 MATERIAL NORM NET WEIGHT VOLUME AREA CREATED MODIFIED APPROVED ECN NUMBER ECN DATE CONCERNING DRAWING FILE ORGANIZATION DEPARTMENT TOLERANCES ABB Oy, Smart Power FIELSP TYPE SCALE FORMAT LANGUAGE SHEET TITLE (FI) 1 : 1 EN/FI REV. TITLE (EN) DOC. NO.
  • Page 66 Pidätämme itsellemme kaikki oikeudet tähän asiakirjaan ja siihen liittyvään informaatioon Reproduction, use or disclosure to third parties without express authority is Asiakirjan toisintaminen, käyttö tai sen sisällön paljastaminen kolmannelle osapuolelle strictly forbidden. © Copyright 2019 ABB. ilman nimenomaista suostumustamme on ehdottomasti kielletty. © Copyright 2019 ABB.
  • Page 67 2021-06-08 Jonna Ojala 2021-06-08 Jonna Ojala 2021-06-08 Timo Jokiniemi ECN NUMBER ECN DATE CONCERNING DRAWING FILE TruBypass ZSDD040-120-1-Z31 ORGANIZATION DEPARTMENT TOLERANCES ABB Oy, Smart Power FIELSP TYPE SCALE FORMAT LANGUAGE SHEET TITLE (FI) 1 : 1 EN/FI REV. TITLE (EN) DOC.
  • Page 68 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
  • Page 69 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — Installation Instruction Bypass-Isolation Automatic Transfer Switches Zenith ZBTS T-series 100-1200A 7.
  • Page 70: Installation

    Use a vacuum cleaner to remove all are installed and properly fastened. debris caused by transport or installation. Each ABB Zenith Bypass-isolation auto- matic transfer switch is factory wired and tested. A complete information package Warning is furnished with each switch which...
  • Page 71: Mounting / Lifting

    Proper lifting equipment must be used to de-energised. mount the Bypass-isolation transfer switch cabinet into place (Note: The weight of 4-pole Standard ABB Zenith By- pass-Isolation automatic transfer switch Warning is 775kg/1709 lb, see the weight informa- Before drilling conduit entry holes or any ac- cessory mounting holes, cover and protect tion in Dimension Drawings ).
  • Page 72: Lifting The Draw-Out Switch

    Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 7.1.2 Lifting the Draw-out Switch Proper lifting equipment must be used to lift the draw-out switch for inspection and servicing (Note: eg.
  • Page 73 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 – Fig. 7.3 Lifting the switch must be performed using an adequate lifting means. The numbers in the picture will tell the different stages of the task.
  • Page 74: Installation

    7.2.1 Power Connections with Screw Type Terminals (as standard) Danger Hazardous voltage may be present. Only an au- ABB Zenith Bypass-isolation automatic thorised electrician may perform the electri- cal installation and maintenance of OX_ auto- transfer switches are supplied with UL matic transfer switches.
  • Page 75: Power Connections With Compression Lugs (Option)

    3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 7.2.2 Power Connections with Compression Lugs (option) ABB Zenith Bypass-isolation automatic transfer switches are supplied as an op- tion for cable lug connections. Below the bolt size and tightening torque for com- pression lugs.
  • Page 76: Ground Connections With Screw Type Terminals

    Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 7.2.3 Ground Connections with Screw 7.2.4 Neutral Connections with Screw Type Terminals Type Terminals ABB Zenith Bypass-isolation automatic ABB Zenith Bypass-isolation automatic transfer switches are supplied with UL transfer switches are supplied with UL listed solderless screw-type ground ter- listed solderless screw-type neutral termi- minal as optional choice.
  • Page 77: Cable Entry From Bottom / Adapter Bay

    3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 7.2.7 Engine/Generator Start Control possible to the connectors, see the con- Connections duit area in picture below.
  • Page 78: Customer Connections, I/O Signals

    Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 7.2.8 Customer Connections, I/O Signals Customer Customer Connections: Connections: Output O1 External supply In ABB Zenith Bypass-Isolation Automatic for Ekip Connections for Fixed and Modules Transfer Switches there are some I/O Draw-out switch connections, which are available for cus- tomer use, if needed.
  • Page 79: Mounting Of Accessories

    3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 8. Mounting of Accessories More information, see animation: Installation of accessories - TruONE™...
  • Page 80: Mounting Of Ekip -Modules To The Fixed Bypass Switch

    Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 8.1.1 Mounting of Ekip –modules to the fixed Bypass switch —...
  • Page 81: Mounting Of The Ekip -Modules To The Draw-Out Switches

    3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 8.1.2 Mounting of the Ekip –modules to the draw-out switches —...
  • Page 82: Wiring Routes Of I/O-Connections / Ekip -Modules Inside The Cabinet

    Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 8.2 Wiring routes of I/O-connections / Ekip -modules inside the cabinet Once all the afterwards added or factory Continue the connections on the...
  • Page 83 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — Maintenance Bypass-isolation automatic transfer switches Zenith ZBTS T-series 100-1200A 9.
  • Page 84: Maintenance

    9. Maintenance — 9.1 Maintenance Principle Warning Warning Due to hazardous voltage and current, ABB Hazardous voltage may be present. Discon- recommends that ABB certified technician or nect all power sources before performing qualified electrician must perform the instal- work inside the Bypass-isolation automatic lation and maintenance.
  • Page 85: Useful Tips For Service Situations

    3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 9.2 Useful Tips for Service Situations These operations are recommended for If the door needs to be opened for service maintenance use only.
  • Page 86: Release The Locking Solenoid

    Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 9.2.2 Release the Locking Solenoid solenoid terminals are situated on the The locking solenoids are located behind back side of the control plate.
  • Page 87: Release The Racking In/Out Push Button

    3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 NOTE! The rack in / out mechanism works only when the switch is in the OFF posi- tion and the other switch is in the I / II position.
  • Page 88: Ekip Signalling 10K

    (with as many Further information on Ekip Signalling LEDs, giving a total of twenty LEDs). 10K is available from the web site http:// www.abb.com/abblibrary/ DownloadCenter/, in particular in the manual 1SDH001318R0002. — Fig. 9.5 Ekip Signalling 10K module...
  • Page 89: Wiring

    3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 Connections The module must be mounted on a DIN rail, and connected by wiring the connec- X14: 5 (+24V DC) tors on the module.
  • Page 90 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Position Description KS01, Pins of the output contact O S01. KS02 KS03, Pins of the output contact O S02.
  • Page 91 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 Position Description Power LED, green. The possible states are: •...
  • Page 92 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Position Description I S01 Signalling LED of the input I S01 physical status, green.The possible states are: •...
  • Page 93: Communication Connectors

    3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 9.3.3 Communication Connectors The communication connectors are posi- tioned on the upper side of the module.
  • Page 94: Dip Switch Configuration When

    Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 9.3.5 DIP switch configuration when installing Ekip Signalling 10K module At installation, the module must be con- figured to communicate via Local Bus or...
  • Page 95: Auxiliary Contact Blocks

    Reproduction, use or disclosure to third parties without express authority is Asiakirjan toisintaminen, käyttö tai sen sisällön paljastaminen kolmannelle osapuolelle strictly forbidden. © Copyright 2019 ABB. ilman nimenomaista suostumustamme on ehdottomasti kielletty. © Copyright 2019 ABB. The auxiliary contact blocks in both Source 2...
  • Page 96: Heater

    Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 9.5 Heater Heater is used for prevention of conden- is turned "ON".
  • Page 97: Meter

    3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 9.6 Meter The multifunction power meter is an ac- Features: cessory, it is designed to be used in elec- •...
  • Page 98: Protection Devices

    Fuse Disconnector is needed for OVR Surge Protection Device. The recom- factory. mended type is: 9.7.1 Surge Protection Device OVR • ABB Fuse Disconnector E93/50 OVR range is designed to prevent electri- - 2CSM277962R1801 E93/50 cal systems and equipment against tran-...
  • Page 99: Integrated Spd, Type Tpme

    3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 9.7.3 Integrated SPD, Type TPME_ 9.7.3.1 Other Features of TPME_ •...
  • Page 100 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
  • Page 101 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — Dimension drawings Bypass-isolation automatic transfer switches Zenith ZBTS T-series 100-1200A 10.
  • Page 102 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 10. Dimension drawings Fig.
  • Page 103 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1...
  • Page 104 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Fig. 10.2 ZS 30-1200, dimension drawings, cabin inside...
  • Page 105 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1...
  • Page 106 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Fig. 10.3 ZS 30-1200, Adapter bay, cable entry from bottom...
  • Page 107 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1...
  • Page 108 Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
  • Page 109 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1...
  • Page 110 With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of infor- mation in this document.
  • Page 111 3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1...
  • Page 112 — Contact us ABB Zenith Controls, Inc. 305 Gregson Drive Cary, NC 27511 24-hour support: ABB Technical Services +1 (800) 637-1738 epis.pqservice@abb.com abb.com/lowvoltage www.abb.com/truone © Copyright 2022 ABB. All rights reserved. Specifications subject to change without notice.

Table of Contents