ABB FBIP-21 BACnet/IP User Manual page 61

Adapter module
Table of Contents

Advertisement

No.
Configuration status
Before restore
3
Replacing a fieldbus adapter with another adapter of the same type. But the new adapter
was used with some other drive previously.
Drive has a backup of FBIP-21 configuration
and a new FBIP-21 with existing configuration
is attached.
4
A new drive and fieldbus adapter are used.
Drive has no backup or a backup of some
other type of fieldbus adapter other than FBIP-
21 exists.
FBIP-21 with no configuration is attached.
5
Replacing drive with a new drive and reusing the old Fieldbus adapter.
Drive has no backup or a backup of some
other type of fieldbus adapter other than FBIP-
21 exists.
FBIP-21 with an existing configuration is at-
tached.
6
Clearing fieldbus configuration from drive and module to defaults.
You can clear the fieldbus configuration from
drive and module to defaults with parameter
96.06 Parameter restore using the selection
Reset all fieldbus settings.
Appendix B - Module configuration backup 61
After restore
Drive backup is used in FBIP-21.
FBIP-21 generates a new backup with its de-
fault settings and copies it to drive.
FBIP-21 copies its backup to drive.
Clears the fieldbus parameters and backup
files for FBA A and FBA B on the drive side. If
a FBIP-21 module is connected, its configura-
tions are reset to defaults.