Bus 2Easy Control Devices; Addressing Control Devices - FAAC E045S User Manual

Table of Contents

Advertisement

SAFEcoder
DL1
DL2
DL3
S800H ENC
DL1
DL2
DL3
Correct connections
DL1
MOT2
DL1
DL2
DL3
MOT1
DL1
DL2
DL3
DL2 on = encoder connected to MOT1
DL2 off = encoder connected to MOT2
E045S
2EASY
DL1
DL2
DL3
2EASY
DL1
DL2
DL3
4
DL1
MOT1
DL1
DL2
DL3
MOT2
DL1
DL2
DL3
 5

BUS 2EASY CONTROL DEVICES

!
Do not use the BUS 2easy line for emergency stop
commands.
1. Configure the DIP switches on the device to assign
1 o 2 commands.
i
Stop NC also generates a stop when the device is
disconnected. A command (e.g.: OPEN A_1) must be
used on only one of the connected devices.
2. Register the device (see specific section).
3. Check the BUS 2easy devices (see specific section)
and make sure that the automation operates ac-
cording to the type of control devices installed.
 7 Addressing Control Devices
Key: 0=OFF , 1=ON
DIP switch 5 enables the device for 1 (OFF )command or 2 (ON)
commands
ON
1 2 3 4 5
0 0 0 0 0 Open A_1
0 0 0 1 0 Open A_2
0 0 1 0 0 Open A_3
0 0 1 1 0 Open A_4
0 1 0 0 0 Open A_5
0 1 0 1 0 Stop
0 1 1 0 0 Stop NC_1
0 1 1 1 0 Stop NC_2
1 0 0 0 0 Close
1 0 0 1 0 Open B_1
1 0 1 0 0 Open B_2
1 0 1 1 0 Open B_3
1 1 0 0 0 Open B_4
1 1 0 1 0 Open B_5
1 1 1 0 0 /
1 1 1 1 0 /
19
ON
1 2 3 4 5
0 0 0 0 1 Open A_1 Open B_1
0 0 0 1 1 Open A_1 Open B_2
0 0 1 0 1 Open A_1 Stop
0 0 1 1 1 Open A_1 Close
0 1 0 0 1 Open A_2 Open B_1
0 1 0 1 1 Open A_2 Open B_2
0 1 1 0 1 Open A_2 Stop
0 1 1 1 1 Open A_2 Close
1 0 0 0 1 Open A_3 Open B_3
1 0 0 1 1 Open A_3 Open B_4
1 0 1 0 1 Open A_3 StopNC_1
1 0 1 1 1 Open A_3 Close
1 1 0 0 1 Open A_4 Open B_3
1 1 0 1 1 Open A_4 Open B_4
1 1 1 0 1 Open A_4 StopNC_2*
1 1 1 1 1 Open A_4 Close
532373 - Rev.A