Technical Data - ABB ODPSE230C Installation And Operating Instructions

Dual power source

Advertisement

Technical data

Voltage and current limits
Rated AC voltage
Output current
Operating time
Main circuit connections
X11:1
X11:2
X13:1
X13:2
X12:1
X12:2
Connection cables
Supply side cables of the main circuit
Load side cables of the main circuit
External transformer
When ODPS230 is used in network where N is not connected an external transformer must be used to drop voltage
level. Transformer has to be Main to Phase transformer and isolative. Effective value depends on the size of the mo-
tor operator. See Connection diagram.
Dielectric properties
Overvoltage category
IEC 60947- 1 Rated impulse withstand voltage (Uimp), basic
insulation
IEC 60947-1 Dielectric test
IEC 60092-504 Insulation resistance measurement
Mechanical characteristics
Material of Enclosure
Degree of protection
Dimensions
Height
Width
Depth
Environmental conditions
Ambient air temperature
Altitude of the site of installation
IEC 60068-2-30 Humidity, relative
IEC 60947-1 Pollution degree
Mechanical tests
IEC 60068-2-6 Vibration test
IEC 60068-2-27 Shock test
Transport and storage
Ambient air temperature
EMC characteristics
IEC 61000-4-2 Electrostatic discharge immunity test
IEC 61000-4-3 Radiated, radio-frequency, electromagnetic
field immunity test
IEC 61000-4-4 Electrical fast transient/burst immunity test
IEC 61000-4-5 Surge immunity test
IEC 61000-4-6 Immunity to conducted disturbances, induced
by radio-frequency fields
IEC 61000-4-8 Power frequency magnetic field immuntiy test Level 4
CISPR 11 Electromagnetic disturbance characteristics
(Emission)
Table 2 Technical data
220 ... 240 V +/-20%, 50/60 Hz +/-10%
Max 4 A
2 s
Line I Phase
Line I Neutral
Line II Phase
Line II Neutral
Motor operator Phase
Motor operator Neutral
0,2 ... 2,5 mm
2
0,2 ... 2,5 mm
2
III
4,0 kV
1,89 kV, 50 Hz, 5 s
> 100 MΩ, 500 V DC
Self-extinguishing thermoplastic, UL 94 V-0
IP 20
90 mm
32 mm
130 mm
-25 ... +60 °C
< 2000 m
< 93 %, T = -25 ... +60 °C
3
5 Hz to 13,2 Hz: +/-1 mm
13,2 Hz to 100 Hz: +/- 0,7 g
Q does not exceed 5
Duration 90 min at 30 Hz or at each resonance fre-
quency
Acceleration 100 m/s
peak (10g
2
(15g
). Pulse duration: 11 ms
n
-40 ... +70 °C
8kV (Level 3) Air discharge
4kV (Level 2) Contact discharge
Level 3
Level 3
2kV Phase to Neutral
Level 3
Group 1 Class B
) and 150 m/s
peak
2
n