22. Press the Up or Down and Left or Right buttons
A
to edit Zone Name (i.e., Living Room). Use this
setting to give a user-friendly name to each used
zone, if desired. Press the Select/Next button to save entry and
proceed.
23. Press the Up or Down button to select the desired
A
GROUP (01-64) for the selected zone. Use this
setting to select the group number that the
selected zone will be assigned to under this configuration. Press the
Select/Next button to save entry and proceed.
24. Press the Up or Down button to select the desired
A
CHANNEL (1-8, X). Use this setting to change the
mapping of the Channel number to the physical
Load connections. Press the Select/Next button to save entry and
proceed.
NOTE: Two Channels cannot be mapped to the same Channel number.
You must first change the Channel to an "X", which is a place holder
(i.e., to change 1 to 6, first change the 6 to an "X", than change the 1 to
a 6. You may now change the 6 to a 1).
25. Press the Up or Down button to select the desired
B
TYPE (REL, DIM). This setting is used to select
either a dimming (dimmer) or a non-dimming
(relay) Load. If a dimmer (DIM) type is selected, press the Select/Next
button to save entry and proceed. If a non-dimming (REL) type is
selected, press the Select/Next button to save entry and proceed to
Step 27.
26. Press the Up or Down button to select the desired
B
LOAD TYPE (FLOR, INC). This setting is used to
select either Incandescent, which is used for
Incandescent, Magnetic Low-Voltage, Cold Cathode, Tungsten and
Neon Loads or Fluorescent, which is used for Mark X™ Fluorescent
Loads. Press the Select/Next button to save entry and proceed. Zone
programming is now finished.
B
27. If programming additional Zones, press the Select/Next button and
repeat Steps 21 through 27.
If Zone programming is complete, press the Wizards button to return to
the Main Screen.
Aux Devices –
A
Used to setup auxiliary zones.
28. Press the Wizards button and then the Up or
Down button to select the SETUP WIZARD. Press
the Select/Next button to access the SETUP
WIZARD.
DI-000-D3208-00A-2/13/02
PROGRAMMING AND OPERATION
23
PANEL: 31 ZONE:1
ZONE # 31-1
SELECT GROUP: 01
ZONE# 31-1
CHANNEL#: 1
ZONE# 31-1
SELECT TYPE: DIM
ZONE# 31-1
LOAD TYPE: <INC>
ZONE# 31-1
V
Use , v or SEL
<SETUP WIZARD>
3/6/02, 11:05 AM