3. Remove Front Door Frame assembly by gently lifting the bottom edge of the
frame until it snaps off (refer to Figure 1). Swing the bottom edge away until
the upper section is released.
4. Mount 5-gang, 2-1/2" wall box with a 4-gang raised cover in wall at desired
location with 4 screws.
5. Line Voltage Wiring:
NOTES:
• The insulation of the Class I field wiring must be rated no less than 75°C.
• Each screw terminal is capable of holding up to two (2) 12 AWG wires.
A. Remove 3/8" (0.95 cm) of insulation from each circuit conductor. Make
sure that ends of conductors are straight.
B. Connect conductors per WIRING DIAGRAM as follows (refer to Figures
2 and 3): Insert conductors under appropriate terminal clamp and
tighten screws to 9 in.-lbs. of torque.
NOTE: The Multizone Controller will automatically assign zone numbers
to loads based on which terminal you connect each load to. For
example: connecting a bank of fixtures to the Load 1 terminal means
that those fixtures will be the first Zone on that Multizone Controller. The
D3208 also allows you to change these zone numbers, if you desire.
6. Low-Voltage Wiring (If LCnet wiring is required):
NOTES:
• LCnet must be wired using a twisted pair for the CAN_H and CAN_L wires.
Leviton recommends using CAT5 wire.
• LCnet wires must also be dressed so they are separate from the high
voltage (Class I) conductors. Refer to local building codes for the
appropriate installation requirements for the low-voltage wiring. Jacketing
over the low-voltage wires may be required to provide appropriate
insulation from the high-voltage wiring.
Connect leads per WIRING DIAGRAM as follows (refer to Figure 3): Insert
each lead into appropriate plug connector location by pushing firmly. If using
stranded wire, twist strands of each lead tightly (making sure that there are
no stray strands) and push firmly into appropriate plug connector location.
Tighten the screws on the plug connector—making sure that no bare
conductor is showing. Connect plug connector to jack on the back of the
Controller.
7. Carefully position all wires to provide room in wall box for Multizone
Controller. Mount Controller to raised cover using the screws provided (refer
to Figure 1).
8. Restore power at circuit breaker or fuse.