Table 34. Trigger Command Word - Register 802; Table 35. Datalogger Module Status - Register 435; Table 36. Fault Disable Bitwise - Register 1096 - Emerson AMPGARD RVSS Instruction Booklet

Reduced voltage soft-starter
Table of Contents

Advertisement

AMPGARD RVSS
Reduced Voltage Soft-Starter
User Manual

Table 34. Trigger command word - register 802

Code
Command
0
Disable Datalogger
1
Wait For Trigger - Save to Next Memory Block
2
Wait For Trigger - Save to Same Memory Block
3
Wait For Trigger - Save to Memory Block 1
4
Wait For Trigger - Save to Memory Block 2
5
Wait For Trigger - Save to Memory Block 3
6
Wait For Trigger - Save to Memory Block 4
7
Wait For Trigger - Save to Memory Block 5
8
Wait For Trigger - Save to Memory Block 6
9
Wait For Trigger - Save to Memory Block 7
10
Wait For Trigger - Save to Memory Block 8
11
Auto Re-Arm After Reset - Save Next Block
12
Auto Re-Arm After Reset - Save Same Block

Table 35. Datalogger module status - register 435

Code
Command
0
Init_mode
1
Stopped
2
Wait_Trigger
3
Pos_Trigger
4
Triggered
5
Preparing_Buffer

Table 36. Fault disable bitwise - register 1096

Bit
Fault disable (add up decimal enter register
1096)
15
Reserved9
14
Reserved10
13
Reserved11
12
Reserved12
11
RVSS Overtemperature
10
LineFreqDev (Undervoltage)
9
LineFreqDev (PLL Phase Error)
8
JAM Inst Overcurrent
7
Amps Unbalance or 1 Ph
6
Voltage Unbalance Or 1Ph
5
Overload Truck EOL
4
Line FreqDev (FreqOutOfRange)
3
Overvoltage
2
UnderVoltage
1
Motor Overload EOL
0
Motor Instantaneous Overcurrent
Register 1096 = 0=>All faults enabled
Register 1096=2047=> Faults bit 0 through Bit 10 disabled
Decimal
32768
16384
8192
4096
2048
1024
512
256
128
64
32
16
8
4
2
1
Instruction Booklet IB020003EN
Effective January 2021
EATON www.eaton.com
97