Setting up an inControl project for Ethernet communications
To set up an inControl project using the Modbus TCP DTM, first follow the same process as that used for Modbus Serial:
open inControl, create a new project (if necessary),
go to the Device tab, and drag the Modbus TCP icon from the Device Catalogue table to the Network View Network node (see Figure 105).
Figure 105. Connect Modbus TCP to Network.
When the Ampgard RVSS node is connected to the Modbus TCP node, the Modbus TCP - Set Address window will appear. Use this window
to enter the IP address set in the BCM Ethernet card using the DIP switches (see Figure 104), and click Set.
Drag the Ampgard RVSS DTM icon from the Device Catalogue to the Modbus TCP node in the Network View (see Figure 106).
Figure 106. Modbus TCP - Set Address window.
With the Modbus TCP DTM connected to the Network, click the DEVICE tab Connect icon to connect the DTM to the network. A green
status bar will indicate success (see Figure 107).