5. Soft Start Configuration
1.
Profile 1 Setting
1. Start ramp time
3. Kick start voltage
4. Kick start time
5. Initial voltage
6. Current limit
11. Stop ramp time
12. Deceleration initial voltage
13. Deceleration final voltage
14. Incomplete sequence time
2.
Profile 2 Setting
1. Start ramp time
5. Initial voltage
6. Current limit
11. Stop ramp time
14. Incomplete sequence time
3.
Transition TH%
4.
Run Transition Dly
5.
Configurable Pre-Start Check
6.
Ramp Transition Speed
7 .
Truck Size
8.
Current Foldback Speed
9.
Transition Type
inControl Startup Wizard
If voltage ramp CL was selected, set time for voltage to ramp from initial to full voltage
If Kick Start was enabled, set kick start voltage level (different from initial voltage)
If Kick Start was enabled, set kick start voltage application time before returning to initial
voltage
If voltage ram CL was selected, set initial voltage for voltage ramp start
If voltage ramp CL was selected, set maximum motor current allowed during a start
If
Linear deceleration voltage soft stop was selected, set time for voltage to ramp from
Deceleration initial to Deceleration final voltage
If
Linear deceleration voltage soft stop was selected, set voltage for initial step down at start
of linear deceleration
If
Linear deceleration voltage soft stop was selected, set output voltage value at which SCRs
switch off and main contactor opens
If voltage ramp CL was selected, set time by which a successful start should have
occurred. Set a time value greater than a typical successful start time, to allow for
temperature differences, but still protect the starter and motor from unusual starting
circumstances.
Instruction Booklet IB020003EN
Effective January 2021