Emerson AMPGARD RVSS Instruction Booklet page 114

Reduced voltage soft-starter
Table of Contents

Advertisement

Instruction Booklet IB020003EN
Effective January 2021
Topic
Parameter
Profile 2
Settings
Faults and
Events
Fault Indicators
Fault Snapshot
1
114
EATON www.eaton.com
Units
Description
Active Fault
Snap Shot Year
Snap Shot Month
Snap Shot Day
Snap Shot Hour
Snap Shot Minute
Snap Shot Second
Current Active Fault
0 = No Faults
1 = E-Stop
2 = RVSS Instantaneous Overcurrent
3 = Motor Instantaneous Overcurrent
4 = Pre-Start Check Fault
5 = Overload
6 = Incomplete Sequence
7 = RVSS Overtemperature
8 = Starts Limit Exceeded
9 = Undervoltage
10 = Overvoltage
11 = Overfrequency
12 = Underfrequency
13 = Phase Rotation Mismatch
14 = Main Failed to close
15 = Bypass Failed to close
16, 17 = Reserved
18 = No Ramp Type is selected
19 = Overload Truck
20 = Volt Unbalance or 1Ph
21 = Amps Unbalance or 1Ph
22 = JAM OC
23 = External Fault
24 - 26 = Reserved
27 = User Interface not available or communications loss with the module
28 - 32 = Reserved
Fault Snap Shot Log Year. The Year from the time stamp information when the last
fault occurred.
Fault Snap Shot Log Month. The Month from the time stamp information when the
last fault occurred.
Fault Snap Shot Log Day. The Day from the time stamp information when the last fault
occurred.
Fault Snap Shot Log Hour. The Hour from the time stamp information when the last
fault occurred.
Fault Snap Shot Log Minute. The Minute from the time stamp information when the
last fault occurred.
Fault Snap Shot Log Second. The Seconds from the time stamp information when the
last fault occurred.
AMPGARD RVSS
Reduced Voltage Soft-Starter
User Manual