b44
Range: 1.0 ~ 10,000 in 1.0
b45
Range: 0.0 ~ 10,000 Sec in 1.0 Sec
b46
Range: 0.0 ~ 100.0 % in 0.1 %
A38
Range: Frequency Lower Limit(A39) ~ Max Frequency(A04) in 0.01 Hz
A39
Range: 0.00 ~ A38 Hz in 0.01 Hz
A40, 42, 44 Skip Output Frequencies
Range: 0.00 ~ Max Frequency(A04) Hz in 0.01 Hz
A41, 43, 45 Skip Frequency Range
Range: 0.00 ~ 10.00 Hz in 0.01 Hz
Current Controller P Gain in DC Braking
Program the current controller P gain in DC braking
This value is applied both brake modes (start and stop)
If motor speed has a large overshoot at DC braking, decrease this value
If value is too big, motor can be vibrated or can't be stopped
 Related Parameters: A33, b42~b46
Current Controller I Gain Time in DC Braking
Program the current controller I gain in DC braking
This value is applied both brake modes (start and stop)
If motor is vibrated or not stop at DC braking, decreased this value
If value is too big, DC braking force can be weak
 Related Parameters: A33, b42~b46
DC Injection Braking Force at Start
Program the level of DC injection braking force of rated electric power of N700E
 Related Parameters:
Frequency Upper Limit
If 0 disable Frequency Limit Function
Program upper limit of an output frequency
 Related Parameters:
Frequency Lower Limit
Program lower limit
 Related Parameters:
Program 3 output frequency values to mitigate different resonance points at which
vibration can cause damages to the equipment such as fans or pumps.
 Related Parameters: A41, A43, A45,
Program skip frequency ranges for A40, A42, and A44 respectively.
 Related Parameters:
Output
Frequency
A38
A39
0Hz
60Hz
Input
0V
10V
4mA
20mA
3-23
Output
Frequency
A45
A44
A43
A42
A41
A40
Setting Frequency