N700E INSTRUCTION MANUAL
A77
Range: 0.0 ~ 100.0 % in 0.1 %
A78
Range: -100.0 ~ 100.0 % in 0.1 %
A79
0.00: Disabled the Low Limit
Range: -100.0 ~ 100.0 % in 0.1 %
A80
0: PID Output Invert Disabled
1: PID Output Invert Enabled
A81
Range: 0.1~ 1000 % in 0.1 %
A82
0.00: Disabled Pre PID Function
Range: 0.00 ~ Max Frequency(A04) in 0.01 Hz
PID Error Limit
Program error limit level, ratio to the maximum error
 Related Parameters:
PID Output High Limit
Program the maximum PID output as a percentage of the maximum output frequency
Related Parameters: A04
PID Output Low Limit
Program the minimum PID output as a percentage of the maximum output frequency
 Related Parameters: A04
PID Output Invert
Program to enable the PID Output Invert
 Related Parameters:
PID Scale Factor
Program the minimum PID output as a percentage of the maximum output frequency(A04)
 Related Parameters: A04
Pre PID Frequency Setpoint
Program the frequency setpoint when PID function is activated. Once the VFD frequency
out reaches this value in A82, PID control function is enabled and the VFD is operated in
closed loop control.
 Related Parameters: A04
RUN Command
[FW,RV]
Output frequency
[d01]
PID feed-back
[d05]
PID operation
PID reference
[A71]
Pre-PID
3-28
ON
Pre PID frequency
[A82]
ON