a.
Align the triangular mark on the heat sink label with the triangular mark on the processor carrier
and processor.
b.
Install the heat sink onto the processor-carrier.
c.
Press the carrier into place until the clips at all four corners engage.
Step 5.
Install the processor-heat-sink module into the system board socket.
Figure 131. Installing a PHM
Rotate the anti-tilt wire bails inward.
Align the triangular mark and four Torx T30 nuts on the PHM with the triangular mark and
threaded posts of the processor socket; then, insert the PHM into the processor socket.
Rotate the anti-tilt wire bails outward until they engage with the hooks in the socket.
Fully tighten the Torx T30 nuts in the installation sequence shown on the heat-sink label.
Tighten the screws until they stop; then, visually inspect to make sure that there is no gap
between the screw shoulder beneath the heat sink and the processor socket. (For reference, the
torque required for the fasteners to fully tighten is 1.1 newton-meters, 10 inch-pounds).
After this task is completed
Proceed to complete the parts replacement (see
Security bezel and dust filter replacement
See this topic to learn how to remove or install the security bezel and the dust filter.
Remove the security bezel
See this topic to learn how to remove the security bezel.
"Complete the parts replacement" on page
Chapter 3
174).
.
Hardware replacement procedures