2.2 Technical Specifications

Input Voltage
Configuration
Mains Voltage Input
Meter Input Power
Current Sensor
Rating
Power Factor
Line Frequency
Meter Accuracy
Voltage Operating
Range
Temperature Range
Relative Humidity
Range
Altitude
Voltage Overload
Pollution Degree
Installation
(Overvoltage)
Category
Measurement
Category
Enclosure Material
Display
Standards
Voltage Ranges
Amperage Ranges
Recommended
In-line Fuse
62-0442—05
2-wire single phase, 3-wire single phase, 3-wire (Delta),
or 4-wire (WYE)
Up To 600 VAC RMS Available
6 VA Maximum
Up To 800 Amps RMS AC
0.5 Leading Or Lagging
50-60 Hz
ANSI C12.20
+/-10% Of Rated Voltage
-30 C To +60 C
0-95% Non-condensing
2000 Meters
+25% Continuously: +100% For 20 Cycles
Degree 2 In Accordance With IEC 664
Category III
Category III
PPO/PS (plastic)
4-Line LCD with backlight
EN 61326-1:2006 IEC 61010-1:2012, 3rd Edition
120 VAC (2-wire single phase)
277 VAC (2-wire single phase) [optional]
120/208-240 VAC (3-wire single phase)
120/208 VAC (4-wire WYE)
127/220 VAC (4-wire WYE)
240 VAC (3-wire Delta)
277/480 VAC (4-wire WYE or 3-wire Delta)
347/600 VAC (4-wire WYE only)
220/380 VAC (4-wire WYE only)
230/400 VAC (4-wire WYE only)
240/415 VAC (4-wire WYE only)
100, 200, 400, 800 Amp
Manufacturer
Mfg. Part No
Rating:
10
Littelfuse
OKLK.500T
500mA, 600VAC Cartridge
Fuse

Advertisement