7.2.11 Changing Password

To change the Password, complete the following steps:
1. Press MENU button.
2. Use UP or DOWN button until the arrow is on the
PASSWORD line.
3. Press SELECT button.
4. Use UP or DOWN button to make changes.
5. Press SELECT button to advance to the next setting. Repeat this step until all
the password settings have been updated.
6. Press MENU to complete the changes. If changes were made, you'll be asked to
save changes.
7. Press UP or DOWN to select 'Y' or 'N'.
8. Press SELECT button to accept the selection. This will return you to the main
menu.
9. Select EXIT to get out of programming mode and return to normal display mode.
*status: <Pwd change OK>, <Pwd not changed>, <Pwd Reset OK>
FIELD RANGE: OLD password=[0000..9999], NEW password=[0000..9999];

7.2.12 Setting BACnet MS/TP

To change the BACnet setting, complete the following
steps:
1. Press MENU button.
2. Use UP or DOWN button until the arrow is on the
BACNET SETTINGS line.
3. Press SELECT button.
Use UP or DOWN button to make changes.
To change by digit, refer to note in Section 7.1 Navigating Menus.
4. Press SELECT button to advance to the next setting. Repeat this step until all
the BACnet settings have been updated.
5. Press MENU to complete the changes. If changes were made, you'll be asked to
save changes.
6. Press UP or DOWN to select 'Y' or 'N'.
7. Press SELECT button to accept the selection. This will return you to the main
menu.
8. Select EXIT to get out of programming mode and return to normal display mode.
FIELD RANGE: MSTP MAC=[0..127]; MAX MASTER=[1..127]
47
DIN-MON™ SMART METER
OLD
NEW
CONFIRM
MSTP MAC
MAX MASTER
PORT
0000
0000
Y
1
127
47808