CLASS 3200 METER

3.0 METER TECHNICAL SPECIFICATIONS

Ordering Information: Define brand, class, input voltage, amperage, protocol, and
sensor type in the format A-BB-CCC-DDDD-E-FFF-GGG, where
A = Brand: E for E-Mon
BB = designates Class: 3200 (32), 3400 (34), or 5000 (50) meter
CCC = input voltage: (208, 480, 600, 120 volt for High Voltage)
DDDD = current rating: (100, 200, 400, 800, 1600, 3200, 25HV)
E = enclosure: J = metal (type 1), R = non-metallic (type 4X), M = MMU
FFF= protocol: RTU = Modbus, BAC = BACnet, EZ7 = proprietary
GGG = Sensors: KIT = split-core, SCS = solid-core, "blank" = none supplied
EXAMPLE:
Input Voltage
Configuration
Mains Voltage Input
Input Power
Current Sensor
Rating
Power Factor
Line Frequency
Metering Accuracy
Temperature Range
Relative Humidity
Range
Altitude
Voltage Overload
Current Sensor
Overload
Pollution Degree
Installation
(Overvoltage)
Category
Measurement
Category
62-0390-02
E-MON
CLASS 3200 METER
INPUT VOLTAGE (208V)
CURRENT RATING (200A)
ENCLOSURE (METAL - TYPE 1)
PROTOCOL (MODBUS)
SENSORS (SPLIT-CORE)
3-wire (delta) Or 4-wire (wye)
Up To 600 VAC RMS available
6 VA maximum rating
Up To 3200 amps RMS AC available
0.5 leading or lagging
50-60 Hz
ANSI C12.20
-20C to +50C
0-95% non-condensing
2000 meters maximum
+25% continuously: +100% For 20 cycles
100% for 1 minute
Degree 2 in accordance with IEC 664
Category III
Category III
E 32- 208 200
8
J
RTU KIT
M33191