Setting Communication Baud Rate; Setting Phase Loss Or Var-Hour Pulse - E-Mon Din-Mon D5 Installation Instructions Manual

Smart meter
Table of Contents

Advertisement

7.2.7 Setting Communication Baud Rate

To change the Communication Baud Rate, complete the
following steps:
1. Press MENU button.
2. Use UP or DOWN button until the arrow is on the
BAUD RATE line.
3. Press SELECT button.
4. Use UP or DOWN button to make changes.
5. Press SELECT button to advance to the next setting. Repeat this step until all
the baud rate settings have been updated.
6. Press MENU to complete the changes. If changes were made, you'll be asked to
save changes.
7. Press UP or DOWN to select 'Y' or 'N'.
8. Press SELECT button to accept the selection. This will return you to the main
menu.
9. Select EXIT to get out of programming mode and return to normal display mode.
FIELD RANGE: BAUD RATE=[9600, 19200, 38400, or 76800]

7.2.8 Setting Phase Loss or VAR-Hour Pulse

To change the Phase Loss or VAR-Hour Pulse, complete
the following steps:
1. Press MENU button.
2. Use UP or DOWN button until the arrow is on the
PHASE LOSS line.
3. Press SELECT button.
4. Use UP or DOWN button to make changes.
5. Press SELECT button to advance to the next setting. Repeat this step until all
the phase loss settings have been updated.
6. Press MENU to complete the changes. If changes were made, you'll be asked to
save changes.
7. Press UP or DOWN to select 'Y' or 'N'.
8. Press SELECT button to accept the selection. This will return you to the main
menu.
9. Select EXIT to get out of programming mode and return to normal display mode.
FIELD RANGE: PHASE LOSS ENABLE=[Y or N], Y=Phase loss, N=VAR-Hour pulse
45
DIN-MON™ SMART METER
BAUD RATE
PHASE LOSS
ENABLE
9600
Y
62-0442—05