4.5.1 Installing Split-Core Current Sensor Assembly
1. Each phase being monitored will require one split-core current sensor assembly.
Open the current sensor assembly by lifting the top off the sensor.
2. Reassemble the current sensor assembly around the conductor(s) to be moni-
tored. Ensure the current sensor side marked "This Side Toward Source" is fac-
ing the source side of the metered conductor.
3. Run the Black and White wires from the current sensors to the meter and install
them according to the standard installation diagram.
P/N
50082281-006
50082281-008
50082281-010
50082281-012
SOURCE
Fig. 14. Typical Split Core Current Sensor.
A
C
Fig. 15. Split Current Sensor Dimensions.
AMPS
A
100
2.00
200
3.25
400
3.25
800
4.75
B
E
D
B
C
2.10
0.60
3.35
1.00
3.35
1.00
5.00
1.20
21
DIN-MON™ SMART METER
LOAD
M35137
M35102
D
E
0.75
0.75
1.25
1.25
1.25
1.25
2.00
2.00
NOTE
62-0442—05