DIN-MON™ SMART METER

7.2.5 Setting Pulse Value

To change the Pulse Value, complete the following steps:
1. Press MENU button.
2. Use UP or DOWN button until the arrow is on the
PULSE VALUE line.
3. Press SELECT button.
4. Use UP or DOWN button to make changes.
To change by digit, refer to note in Section 7.1 Navigating Menus.
5. Press SELECT button to advance to the next setting. Repeat this step until all
the pulse value settings have been updated.
6. Press MENU to complete the changes. If changes were made, you'll be asked to
save changes.
7. Press UP or DOWN to select 'Y' or 'N'.
8. Press SELECT button to accept the selection. This will return you to the main
menu.
9. Select EXIT to get out of programming mode and return to normal display mode.
FIELD RANGE: OUT CHANNEL=[1 or 2], WHr/P=[0.00001..999.99999]

7.2.6 Setting Communication Protocol

To change the Communication Protocol, complete the
following steps:
1. Press MENU button.
2. Use UP or DOWN button until the arrow is on the
PROTOCOL line.
3. Press SELECT button.
4. Use UP or DOWN button to make changes.
5. Press SELECT button to advance to the next setting. Repeat this step until all
the protocol settings have been updated.
6. Press MENU to complete the changes. If changes were made, you'll be asked to
save changes.
7. Press UP or DOWN to select 'Y' or 'N'.
8. Press SELECT button to accept the selection. This will return you to the main
menu.
9. Select EXIT to get out of programming mode and return to normal display mode.
FIELD RANGE: RS-485=[EZ7, Modbus or BACnet]; Ethernet=[EZ7, Modbus or
BACnet]
62-0442—05
44
OUT CHANNEL
USE DEFAULT
WHr/P
1.95313
RS-485
MODBUS
ETHERNET
MODBUS
1