omi ED Series Instruction Manual page 30

Direct expansion compressed air dryers
Hide thumbs Also See for ED Series:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 21
s.r.l.
s.r.l.
s.r.l.
s.r.l.
CF04
CF05
CF06
CF07
CF08
CF09
CF10
CF11
CF12
CF
CF13
Configuration
CF14
Parameters
CF15
CF16
CF19
CF20
CF22
CF23
CF24
CF25
CF26
CF27
CF28
CF29
CF30
CF32
CF33
CF34
CF35
CF36
CF37
26/89
PB1 probe configuration (DEW POINT)
0 = Probe absent
1 = NTC temperature
PB2 probe configuration (AIR INLET)
0 = Probe absent
1 = NTC temperature
PB3 probe configuration (AMBIENT)
0 = Probe absent
5 = NTC temperature
PB4 probe configuration (REFRIGERANT CIRCUIT SUCTION)
0 = Probe absent
1 = NTC temperature
ID1 digital input configuration (1S2)
0 = refrigerant circuit thermal protection
ID2 digital input configuration (REMOTE ON/OFF)
3 = remote on/off
ID5 digital input CONFIGURATION (1Q2 – FAN THERMAL PROT.)
1 = Fan thermal protection
N.U:
ID1-MF digital input polarity (1S2)
0 = active with close contact
1 = active with open contact
ID2-MF digital input polarity (REMOTE ON/OFF)
0 = active with close contact
1 = active with open contact
ID3 digital input polarity (1P1)
0 = active with close contact
1 = active with open contact
ID4 digital input polarity (1P3)
0 = active with close contact
1 = active with open contact
ID5 digital input polarity (1Q2 – FAN THERMAL PROTECTION)
0 = active with close contact
1 = active with open contact
PB4 polarity (REFRIGERANT CIRCUIT SUCTION)
0 = active with close contact
1 = active with open contact
Condensate drain valve/s relais polarity(RL4)
0 = active with close contact
1 = active with open contact
Refrigerant pressure value = 4ma
Refrigerant pressure value = 20ma
PB1 probe calibration offset (DEW POINT)
PB2 probe calibration offset (AIR INLET)
PB3 probe calibration offset (AMBIENT)
PB4 probe calibration offset (REFRIGERANT CIRCUIT SUCTION)
Condensate drain unit operation
0 = Always ON
1 = Timed
Condensate drain ON - time
Condensate drain OFF - time
Selection: ° C or ° F
0 = ° C / BAR
1 = ° F / psi
Selection of mains frequency
0 = 50 Hz
1 = 60 Hz
2 = Direct current
Serial address
Remote controller
0 = 4 buttons
1 = 6 buttons
2 = 6 buttons with NTC probe on board
Default controller display
0 = IN / PROBE
1 = OUT / PROBE
2 = IN / rtC
3 = OUT / rtc
Firmware release
Cod. 710.0103.01.01 – Rev.04 – 09.2012
ED – DXL AL
ED
ED
ED
serie
1
1
5
1
0
3
1
4
1
1
1
0
0
1
0
0
bar
30
bar
-1
° C
0
° C
0
° C
0
° C
1
1
Sec
300
Sec
0
2
1
1
0
2.0

Advertisement

Table of Contents
loading

Table of Contents