Information About Remaining Risks Of The Equipment; Transportation; Delivery And Handling; Package Disposal - omi ED Series Instruction Manual

Direct expansion compressed air dryers
Hide thumbs Also See for ED Series:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 21
s.r.l.
s.r.l.
s.r.l.
s.r.l.

2.3 Information about remaining risks of the equipment

Fire:
This equipment is not supplied with freon drain safety valve (in accordance to EN-378-2).
In case of fire it is preferable to use fire extinguishers or extinction systems composed of powder, foam or carbon dioxide. It is also possible to cool
the equipment with nebulised water.
Avoid the massive use of water. In case of freon gas leak the chemical reaction can cause caustic effects.
Before any intervention wait till the temperature of the ambient and machine have been reduced.
Therefore it is preferable to insert the dryer into the Fire Prevention and Factory Safety Plan.
Arrange adequate actions to prevent and fight the possible risk.
Dispersion of freon gas in the ambient:
The refrigerant is toxic only if inhaled at high concentration: it is necessary to provide an adequate ventilation in the room where the equipment is
installed.
In any case check the scheme showing the values and risks.
Excessive pressure on the compressed air side:
This equipment is not supplied with safety devices on the compressed air side.
The safety devices on the compressed air side must be carried out by the user.
Such devices will have to be carried out according to the applicable National Norms and to the limits mentioned in this manual.
Ozone layer deterioration:
The adoption of HFC freon causes ozone layer deterioration and the greenhouse effect.
EN378-1:2000
FREON
R-134a
R-507
R-404a
R-407c

3.0 TRANSPORTATION

3.1 Delivery and Handling

The dryer has to be handled in an upright position using a means of transportation with a suitable lifting power (see technical data).
Removing the carton from the top and moving the dryer from the wooden pallet into the chosen position (always wear safety gloves and eye
protection).

3.2 Package Disposal

Dispose the various material in compliance with the relevant rules locally in force.

3.3 Return of damaged Equipment/Machines

Repack the dryer in its original carton or with one of the same dimensions.
The dryer must be kept vertical and packed as supplied from the manufacturer.
Do not transport the dryer without proper packaging, shipment damage remains in responsibility of the sender.
Materials returned without proper packaging and authorization documents will not be accepted.

4.0 SET-UP AND START-UP

4.1 Machine positioning

The dryer should be placed in a suitable room with the following features:
A flat and capable seating base to hold weight of the machine.
The machine must be protected from atmospheric agents and should not directly be exposed to the sun light.
A clean, dry and properly vented site: Temperature of +5 to +50° C (we suggest to blow the warm air to the outside).
Make sure you will leave sufficient clearance around the dryer in order to allow an adequate cooling of the machine as well as for maintenance
and/or control operations.
19/89
GRUOP
L
safety
1
A1
1
A1
1
A1
1
A1
Cod. 710.0103.01.01 – Rev.04 – 09.2012
COMPOSITION
1,1,1,2-tetrafluoroethane
R-125/R-143 a (50/50)
R-125/143a/134 a (44/52/4)
R-32/125/134 a (23/25/52)
ED – DXL AL
ED
ED
ED
AUTO IGNITION
GWP
TEMPERATURE (° C)
743
1300
-
3800
728
3800
704
1600
serie
ODP
0
0
0
0

Advertisement

Table of Contents
loading

Table of Contents