1 Principles of Operation
1.1

Introduction

The RM2048HE is a telecommunications grade rectifier with the following features:
High Efficiency
Hot Pluggable
Forced Air Cooled
Thermally Protected
Power Factor Corrected
Wide input AC Voltage
Constant Power Output Limit
Input/Output Voltage and Current Protected
Active Load Sharing
Serial alarm and control interface
Microprocessor controlled
1.2

Indicators

There are 3 LED indicators on the front panel indicate the operational state of the rectifier.
This green LED indicates that mains power is connected to the unit and that the primary stages of the
rectifier are operating.
This LED flashes during power save mode.
This yellow LED indicates a non-Urgent alarm state within the rectifier. This could be caused by the
following:
Rectifier in output power/current limit
Rectifier over temperature
Fan failed
Rectifier soft starting
No communications address (LED is flashing in this state)
Brownout
Postmate open
This red LED indicates an Urgent alarm state within the rectifier. This could be caused by the following:
Rectifier Failed
The AC input voltage is outside the operating range.
Rectifier shut down due to output over voltage or over temperature.
1.3

Power and Current Limit

The rectifier automatically limits its output as load demand reaches it maximum capacity.