Object type of the output:
Options:
The parameter is used to specify whether the output object sends a 1-bit value (0/1) or a 1-
byte value (0 - 255).
–
1 bit: The following supplementary parameters are available:
Sending value when input 1 > input 2:
Options:
The parameter is used to specify which output object is sent (ON or OFF) when input 1
is logically larger than input 2.
Sending value when input 1 < input 2:
Options:
The parameter is used to specify which output object is sent (ON or OFF) when input 1
is logically smaller than input 2.
–
1 byte: The following supplementary parameters are available:
Sending value when input 1 > input 2:
Options:
The parameter is used to specify which output object is sent when input 1 is logically
larger than input 2.
Sending value when input 1 < input 2:
Options:
The parameter is used to specify which output object is sent when input 1 is logically
smaller than input 2.
Telegram is sent at:
Options:
A telegram is sent when the selected condition is met.
Cyclic sending of output:
Options:
The parameter is used to specify whether the output telegram is sent in cycles.
–
Deactivated: No additional parameters available.
–
Activated: The following parameter appears:
Product manual 2CKA00xx73xxxxx
KNX control elements and application parameters
1 bit
1 byte
OFF telegram
ON telegram
OFF telegram
ON telegram
Setting options from 0 - 255
Setting options from 0 - 255
Change output
Output 1 is larger than input 2
Output 1 is smaller than input 2
Deactivated
Activated
Application "Logical functions"
│207