Sent value 1:
Options:
Switchover: At each actuation a switchover takes place between the two set values
"Object type 1" and "Object type 2".
0 / 1: Switching commands are sent with 1 bit (0 or 1), e.g. for switching a switching
actuator.
Sent value 2:
Options:
0 / 1: Switching commands are sent with 1 bit (0 or 1), e.g. for switching a switching
actuator.
Forced operation: Management systems can access the device directly via KNX. However,
it can also be specified that one can select manually (forced operation) via buttons. The
following supplementary parameter is available:
Sent value 1 / value 2:
Options:
1-byte value [0% - 100%]: A value is sent as 1-byte value without a sign (percentage value).
The following supplementary parameter is available:
Sent value 1 / value 2 [0 - 100%]:
Options:
1-byte value [0 - 255]: A value is sent as 1-byte value without a sign, e.g. an actuating value,
angle or brightness value. The following supplementary parameter is available:
Sent value 1 / value 2 [0 - 255]:
Options:
1-byte value [-128 - 127]: A value is sent as 1-byte value with a sign, e.g. an actuating
value. The following supplementary parameter is available:
Sent value 1 / value 2 [-128 - 127]:
Options:
Scene number: The parameter is used to select a 1-byte object to link it with a scene
number. Values between 1 and 64 are available for light scene numbers. The following
supplementary parameter is available:
 
Product manual 2CKA00xx73xxxxx
KNX control elements and application parameters
Switchover
0
1
0
1
ON, forced operation active
OFF, forced operation active
Deactivate forced operation
Setting option from 0 - 100
Setting option from 0 - 255
Setting option from -128 - +127
"Switch" control element