MGE UPS Systems Pulsar Evolution 1100 Tower Installation And User Manual

MGE UPS Systems Pulsar Evolution 1100 Tower Installation And User Manual

Mge ups systems installation and user manual pulsar evolution 1500 tower/1500 rack 1100 tower/1100 rack 800 tower/800 rack 500 rack

Advertisement

www.mgeups.com
MGE
UPS
SYSTEMS
Pulsar Evolution
1500 Tower/1500 Rack
1100 Tower/1100 Rack
800 Tower/800 Rack
500 Rack
Installation and user
manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Pulsar Evolution 1100 Tower and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for MGE UPS Systems Pulsar Evolution 1100 Tower

  • Page 1 SYSTEMS Pulsar Evolution 1500 Tower/1500 Rack 1100 Tower/1100 Rack 800 Tower/800 Rack 500 Rack Installation and user manual...
  • Page 2: Important Safety Instructions

    Pulsar Evolution at the end of its service life. To discover the entire range of MGE UPS SYSTEMS products and the options available for the Pulsar Evolution range, we invite you to visit our web site at www.mgeups.com or contact your MGE UPS SYSTEMS representative.
  • Page 3 CAUTION: Safety of persons The UPS has its own internal power source (the battery). Consequently, the power outlets may be energized even if the UPS is disconnected from the AC-power source. Dangerous voltage levels are present within the UPS. It should be opened exclusively by qualified service personnel. The UPS must be properly earthed.
  • Page 4: Using This Document

    Foreword Using this document Information may be found in two ways, using: the contents; the index. Pictograms Important instructions that must always be followed. Information, advice, help. Visual indication. Action. Audio indication. In the illustrations on the following pages, the symbols below are used: LED off.
  • Page 5: Table Of Contents

    Presentation Overall view ... 7 Tower models ...7 Rack models ...7 Back ... 8 Control panel ...9 Installation Unpacking and parts check ...10 Tower models ...10 Rack models ...11 Installation ...12 Tower models ...12 800/1100/1500 Rack models...13 500 Rack model ...14 Connecting the protected equipment ...15 Connection to the RS232 or USB communications port (optional) ...16 Connection to the data-line protection port (optional)...16...
  • Page 6 Contents Maintenance Trouble-shooting ...22 Replacement of the battery module ...23 Tower models ...23 Rack models ...25 Environment Appendices Technical data Simplified diagram...28 Technical characteristics ...29 Examples of battery backup times ...30 Glossary ...31 Index ...32 Page 6 - 3400723200/AC ...27...
  • Page 7: Presentation

    1. Presentation Dimensions in inches (W x H x D) Evolution 800 Tower 5.9 x 9.3 x 16.3 Evolution 1100 Tower 5.9 x 9.3 x 16.3 Evolution 1500 Tower 5.9 x 9.3 x 19 Weight in lbs Evolution 800 Tower Evolution 1100 Tower 25.4...
  • Page 8: Back

    1. Presentation 1.2 Back Pulsar Evolution 800 / 1100 / 1500 Tower Pulsar Evolution: Pulsar Evolution 500 / 800 / 1100 Rack Pulsar Evolution 1500 Rack 34Z5 U.P.S. AC Input Vac IN AC Output Page 8 - 3400723200/AC Vac OUT I max 12A U.S.
  • Page 9: Control Panel

    1.3 Control panel Illuminated ON/OFF button for the receptacles. Operation on battery power. UPS fault. Battery fault. Overload. Group 1 programmable receptacles supplied with power. Group 2 programmable receptacles supplied with power. Booster or fader mode. Bargraph indicating percent load at output. Bargraph indicating the battery charge level.
  • Page 10: Installation

    2. Installation 2.1 Unpacking and parts check Tower models RS232 communications cable for Windows Operating Systems. For Unix/Linux Operating Systems, please order for free the following part number: 66090 USB communications cable. CD-ROM with the Solution-Pac and UPS Driver software. Product documentation.
  • Page 11: Rack Models

    Rack models RS232 communications cable for Windows Operating Systems. For Unix/Linux Operating Systems, please order for free the following part number: 66090 USB communications cable. CD-ROM with the Solution-Pac and UPS Driver software. Product documentation. Telescopic rails for mounting in 19" bay with mounting hardware. Securing system for equipment power cords.
  • Page 12: Installation

    2. Installation 2.2 Installation Tower models Page 12 - 3400723200/AC io n lu t E v o...
  • Page 13: 800/1100/1500 Rack Models

    Follow steps 1 to 6 for rack mounting of the UPS on the rails. The rails and the necessary mounting hardware are supplied by MGE UPS SYSTEMS. For step 1, screw quantity shown is for 1500 VA. 800 and 1100 VA use two screws for each side.
  • Page 14: 500 Rack Model

    2. Installation 500 Rack model Follow steps 1 to 3 for rack mounting of the UPS on the rails. Floor Mount Configuration Wall Mount Configuration Page 14 - 3400723200/AC...
  • Page 15: Connecting The Protected Equipment

    2.3 Connecting the protected equipment A Pulsar Evolution 1500 tower UPS has been used below to illustrate the instructions. The principle is the same for all the other tower and rack models. Check that the indications on the rating plate on the back of the UPS correspond to your AC-power system and to the actual electrical consumption of all the equipment to be connected to the UPS.
  • Page 16: Connection To The Rs232 Or Usb Communications Port (Optional)

    21 or 22 to the RS232 2 or USB 1 communications port on the UPS. The UPS can now communicate with all MGE UPS SYSTEMS supervision, set-up or safety software. The data-line protection function on the UPS eliminates overvoltages flowing on the com- puter-network lines.
  • Page 17: Installation Of The Communications-Card Option

    2.6 Installation of the communications-card option Vac OUT I max 12A U.S. PAT. NO. 6,094,363 Reseau Volt 120V~1O Mains Amps 12A MAX Netz Hertz 50/60 Hz Util Volt 120V~1O Load Hertz 50/60 Hz Ausg W/VA 1000W/1440VA 344-50254-00 Data line protection It is not necessary to shut down the UPS to install the communications card.
  • Page 18: Operation Start-Up

    3. Operation 3.1 Start-up Note: The battery is charged as soon as the UPS is connected to the AC-power source, even if button 10 is in the OFF position. 3.2 Shift to booster or fader mode (during voltage variations in the AC-input power) Page 18 - 3400723200/AC Press the ON / OFF button 10 .
  • Page 19: Operation On Battery Power (Following Failure Of Ac-Input Power)

    3.3 Operation on battery power (following failure of AC-input power) Transfer to battery power Threshold for the low-battery warning The UPS automatically restarts when power returns. If the UPS does not restart, check that the “automatic restart when power returns” function has not been disabled (see sec- tion 3.4 Personalization).
  • Page 20: Personalization (Optional)

    3. Operation 3.4 Personalization (optional) Function Personalization parameters can be set and modified using the UPS Driver software installed on a computer that is connect- ed to the UPS (see section 2.4 Connection to the RS232 or USB communications port). Check that the RS232 21 communications cable is connected.
  • Page 21: Voltage-Thresholds Tab

    Voltage-thresholds tab Configurable function Output voltage on battery power Upper threshold for transfer to battery power Fader-mode cut-in threshold Booster-mode cut-in threshold Lower threshold for transfer to battery power Maximum input-voltage range (1) Lower threshold for transfer to battery mode = 70 V Sensitivity tab Configurable function UPS sensitivity level...
  • Page 22: Maintenance Trouble-Shooting

    4. Maintenance 4.1 Trouble-shooting Troubleshooting not requiring MGE UPS SYSTEMS after-sales support (all versions) Indication LED 13 flashes and the buzzer beeps once. LED 12 flashes. Troubleshooting requiring MGE UPS SYSTEMS after-sales support Indication LED 12 goes ON and the buzzer sounds contin- uously.
  • Page 23: Replacement Of The Battery Module

    4.2 Replacement of the battery module Tower models Safety rules Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and required precautions. Keep unauthorized personnel away from batteries. Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high. Precautions must be taken for all handling: remove all watches, rings, bracelets and any other metal objects;...
  • Page 24 4. Maintenance Installation of the new battery module Carry out the above operation in reverse order. CAUTION: risk of electric arc when connecting the battery. To maintain an identical level of performance and safety, use a battery module identical to that previously mounted in the UPS.
  • Page 25: Rack Models

    Rack models Removal of the battery module This operation may be carried out with the UPS supplying power to the load. A - Unclip the small plate with the MGE logo on the front panel of the UPS. B - Remove the two screws. C - Remove the left-hand side of the front panel by pulling it forward.
  • Page 26 4. Maintenance Installation of the new battery module Carry out the above operation in reverse order. CAUTION: risk of electric arc when connecting the battery. To maintain an identical level of performance and safety, use a battery module identical to that previously mounted in the UPS.
  • Page 27: Environment

    UPS recycling at the end of service life: MGE UPS SYSTEMS undertakes to recycle, by certified companies and in compliance with all applicable regulations, all UPS products recovered at the end of their service life (contact your MGE branch office).
  • Page 28: Appendices

    6. Appendices 6.1 Technical data Simplified diagram Filter Booster / fader transformer Input Output Inverter Charger Battery Page 28 - 3400723200/AC...
  • Page 29: Technical Characteristics

    <40 dBA 0 to 35° C 20 to 90% 6. Appendices 1500 Tower/1500 Rack 1100 Tower/1100 Rack 1100 VA / 700 W 1500 VA / 1000 W 2 x 12 V - 9 Ah, 3 x 12 V - 9 Ah,...
  • Page 30: Examples Of Battery Backup Times

    6. Appendices Examples of battery backup times Pulsar Evolution 500 2 rack-optimized dense servers 1 router 1 hub Pulsar Evolution 800 3 rack-optimized dense servers 2 file/print servers 1 data server + 1 hub + 1 router 1 router 1 hub Pulsar Evolution 1100 3 rack-optimized dense servers 2 file/print servers...
  • Page 31: Glossary

    Receptacle that allows you to connect the equipment you want to protect. For UPS connection to a computer via the serial port. MGE UPS SYSTEMS safety, set-up and supervision software suite on the CD-ROM supplied with the UPS. Uninterruptible Power Supply.
  • Page 32: Index

    6. Appendices 6.3 Index Automatic start ...20 Bargraph...9 Battery Backup time ...30 End of backup time...19 Fault ...9 Personalization ...20 Recycling ...27 Replacement ...22, 23, 24 Threshold for low-battery warning ...19 Transfer to battery power ...9, 19 Buttons ...9 Buzzer ...19 Circuit breakers Battery circuit breaker...8 Input circuit breaker ...8...
  • Page 36 1660 Scenic Avenue Costa Mesa, CA 92626 www.mgeups.com...