3.5 Upsilon STS customization
1 - Press the menu button 26 .
2 - Select "Setup", then "Customization" using the function buttons 23 marked
3 - Confirm the order by pressing the function button 23 marked
4 - Enter the password.
The password
Select "Setup", then "Password" to personalise the password.
Nominal voltage
Overvoltage threshold
Undervoltage threshold
Nominal frequency
Overfrequency threshold
Underfrequency threshold
Phase sync tolerance
Retransfer
Return to preferred source after transfer
Nominal source voltage
Overvoltage threshold
Undervoltage threshold
Nominal source frequency
Frequency tolerances
Phase error tolerance between the two sources
All manuals and user guides at all-guides.com
Ø
Ø
Ø
PERSONALIZATION
Current settings
400 V
10%
10%
50 Hz
5%
E
S
5%
C
15°
YES
or
.
.
is set in the factory.
Factory setting
Automatic
400 V
Un +10%
Un -10%
50 Hz
±5%
±15°
3. Operation
The monitoring parameters must
be identical for the two sources.
These parameters depend on the
tolerances of the connected loads.
Customization
Manual / Automatic
380 / 400 / 415 V
Un +5% to Un +20%
in 1% steps
Un -5% to Un -20%
in 1% steps
50 / 60 Hz
+1% to +10%
-1% to -10%
in 0.5% steps
±1° to ±45° in 1° steps
- Page 23
34020113EN/AA
Need help?