Configuring Volumetric Flow Measurement
6.4.2

Sampler panel

The Sampler panel is shown in Figure 6-5. This panel is used to set up a discrete output to send a
pulse to another device, for example, to control a gas sampler or an odorizer. Whenever the value
configured for
time period specified in
are listed and defined in Table 6-5.
Figure 6-5
Sampler panel
Table 6-5
Sampler parameters
Parameter
Description
Sampler Control
• Enabled: The sampler will use and control the built-in DO
located at point B4.
• Disabled: The sampler will not use and control the built-in DO.
In this case, an FST must be written to send sampler data to a
different DO.
Sampler Volume
Specify the number of cubic feet (U.S. units) or cubic meters
Accumulation
(metric units) of gas to be metered between pulses.
Sampler Duration
Specify the number of seconds that the pulse will be ON.
56
Sampler volume accumulation
Sampler duration
is exceeded, the discrete output is turned on for the
. Only one pulse is transmitted. Parameters on this panel
Micro Motion
Comments
Ensure that the DO used by the
sampler is correctly wired to an
appropriate receiving device. See
the Model 3711 installation
manual.
This value is based on the
instantaneous base flow rate.
Only one pulse is transmitted.
®
Model 3711 Gas Flow Computers