Using The Optional Dial-Up Modem; Managing User Programs - Emerson Micro Motion 3711 Configuration And Use Manual

Gas flow computers
Table of Contents

Advertisement

Administration
Table 14-3
Flags window – Advanced panel
Parameter
Description
CRC Check
• Enabled: Cyclical Redundancy Checking is performed on all
communications using ROC protocol.
• Disabled: No CRC is performed.
I/O Scanning
• Enabled: All I/O scanning is performed as configured.
• Disabled: No I/O scanning is performed. The most recent
values are used in Model 3711 processing until scanning is
resumed.
Pass Through
Click the radio button for the pair of com ports to be used in
Mode
passthrough mode. The first port in the pair is the receiving port
and the second port is the transmitting port. Any messages
receiving on the receiving port will be automatically transmitted
to all devices that are connected to the transmitting port.
Set RTS High for
Used to activate the RTS (Request to Send) signal for
30 Secs
30 seconds. To use it, check the port that you want to activate,
then click Apply.
Power Saving
Not applicable to the Model 3711.
Mode
14.8

Using the optional dial-up modem

The optional dial-up modem can be controlled using industry-standard AT command software, which
is compatible with EIA document TR302.2/88-08006. The Config Command field on the dial-up
modem panel (see Figure 4-2) is used to enter the commands.
Before powering up the Model 3711, ensure that the modem is set to Auto Answer (the default mode
for the dial-up modem card). Micro Motion recommends that modem status be checked periodically
to ensure that it is in Auto Answer mode.
14.9

Managing user programs

The User Programs panel in the Flags window is shown in Figure 14-3. This panel allows you to
enable or disable specific user programs. For the Model 3711, the Calc User Program and the COM1
User Program must always be enabled.
164
Comments
ROCLINK 800 uses ROC protocol
to communicate with the
Model 3711. Other programs may
use ROC protocol or Modbus
protocol.
See Section 4.7 for more
information on pass through mode.
®
Micro Motion