Accessories Connection Diagram; Stator Thermostats; Bearing Thermostats; Stator Thermoresistances - WEG AG10 Series Installation, Operation And Maintenance Manual

Synchronous alternators
Table of Contents

Advertisement

Available languages

Available languages

www.weg.net

4.8.3 Accessories connection diagram

Accessories terminals
16 up to 19 – Space heaters
20 up to 35 – Stator thermoresistance (PT100)
36 up to 51 – Stator thermistors (PTC)
52 up to 67 – Stator thermostats
68 up to 71 – Bearing thermoresistance (PT100)
72 up to 75 – Bearing thermistors
76 up to 79 – Bearing thermostats
88 up to 91 – Thermometers
94 up to 99 – Current transformers

4.8.3.1 Stator thermostats

1 per phase
R
52
53
54
R
5 2
IN SERIES
2 per phase
R
52A
53A
54A
ALARM
R
52D
53D
54D
SHUTDOWN
2 per phase in series
ALARM
SHUTDOWN
32 l Installation, operation and maintenance manual – Synchronous Alternator – AG10 line - Horizontal
S
T
55 56
57
S
T
5 3
S
T
55A 56A
57A
S
T
55D 56D
57D

4.8.3.2 Bearing thermostats

1 per bearing
76
77
FRONT

4.8.3.3 Stator thermoresistances

1 per phase
S
R
20
21
22
1 per phase (3 cables)
R
20
20
21
22
22

4.8.3.4 Bearing thermoresistances

1 per bearing
68
69
FRONT
1 per bearing (3 cables)
6 8
6 8
69
FRONT
ATTENTION
The identification of the PTC sensor terminals
is showed in the item 4.8.3.
When using 2 sensors per phase are added
the suffixes A to alarm and D for shutdown.
For alternators supplied with specific
connection diagram, this takes precedence
over the connection diagrams of this manual.

4.8.3.5 Space heaters

78
79
REAR
T
23 24
25
S
T
23
24
24
25
70
71
REAR
70
7 0
7 1
REAR
12638144