Software Release:
[Application Version 2.8.10128; Configuration Version 2.8.10457]
•
Post Warm-up Lockout Delay (setup):This delay begins timing when the warm-up
delay expires. During this delay, the selected function is ignored. When this delay
expires, the selected function is armed. During the duration of this delay, the selected
function can cycle from active to not active and not reset the delay.
•
Bubble Lockout Delay (setup): This delay begins timing when the selected function is
active. If the selected function is removed during this delay, the delay resets to zero.
If the selected function remains active throughout this delay, the selected action will
occur.
User Interface
The keypads on the MPC-10 / TEC-10 are comprised of 11 tactile buttons. This section describes the
functions of each button.
The buttons have the following functions:
•
Start Key – Allows the operator to start sequence in Manual Mode or initiate an
auto start sequence when in Auto Mode.
•
Stop Key – Allows the operator to initiate the stop sequence in either mode of
operation. As a safety feature, the stop key will skip the cool-down state when it
is pressed twice or held in auto mode. Once shut down, the controller will enter
manual mode to eliminate an auto crank condition if the auto start condition is still
present.
•
Auto Key – Allows the operator to change from Auto to Manual or Manual to Auto
Mode by press-hold for 3 seconds.
•
Alarm Silence Key – Allows the operator to acknowledge alarms on the controller
when warnings and shutdowns are present.
Section 40
2016-04-19
Figure 1: User Interface